6.2.8 3-** Reference/Ramps

Parameter
Number

Parameter Description

Default Value

2 Setup

Change During
Operation

Conver-

sion

Index

Type

3 - 00

Reference Range

[0] Min - Max

All set-ups

TRUE

-

Uint8

3 - 02

Minimum Reference

0

All set-ups

TRUE

-3

Int32

3 - 03

Maximum Reference

50

All set-ups

TRUE

-3

Int32

3 - 10

Preset Reference

0%

All set-ups

TRUE

-2

Int16

3 - 11

Jog Speed [Hz]

5 Hz

All set-ups

TRUE

-1

Uint16

3 - 12

Catch up/slow Down Value

0%

All set-ups

TRUE

-2

Int16

3 - 14

Preset Relative Reference

0%

All set-ups

TRUE

-2

Int16

3 - 15

Reference Resource 1

[1] Analog in 53

All set-ups

TRUE

-

Uint8

3 - 16

Reference Resource 2

[2] Analog in 60

All set-ups

TRUE

-

Uint8

3 - 17

Reference Resource 3

[11] Local bus reference

All set-ups

TRUE

-

Uint8

3 - 18

Relative Scaling Reference Re-
source

[0] No function

All set-ups

TRUE

-

Uint8

3 - 40

Accel/Decel 1 Pattern

[0] Linear

All set-ups

TRUE

-

Uint8

3 - 41

Accel Time 1

3 s

All set-ups

TRUE

-2

Uint32

3 - 42

Decel Time 1

3 s

All set-ups

TRUE

-2

Uint32

3 - 50

Accel/Decel 2 Pattern

[0] Linear

All set-ups

TRUE

-

Uint8

3 - 51

Accel Time 2

3 s

All set-ups

TRUE

-2

Uint32

3 - 52

Decel Time 2

3 s

All set-ups

TRUE

-2

Uint32

3 - 80

Jog Accel/Decel Time

3 s

All set-ups

TRUE

-2

Uint32

3 - 81

Quick Stop Ramp Time

3 s

1 set-up

TRUE

-2

Uint32

6.2.9 4-** Limits/Warnings

Parameter
Number

Parameter Description

Default Value

2 Setup

Change During
Operation

Conver-

sion

Index

Type

4 - 10

Reverse Lock

[2] Both directions

All set-ups

FALSE

-

Uint8

4 - 12

Motor Speed Low Limit [Hz]

0 Hz

All set-ups

FALSE

-1

Uint16

4 - 14

Motor Speed High Limit [Hz]

65 Hz

All set-ups

FALSE

-1

Uint16

4 - 16

Torque Limit Motor Mode

150%

All set-ups

TRUE

0

Uint16

4 - 17

Torque Limit Generator Mode

100%

All set-ups

TRUE

0

Uint16

4 - 50

Warning Current Low

0 A

All set-ups

TRUE

-2

Uint32

4 - 51

Warning Current High

26 A

All set-ups

TRUE

-2

Uint32

4 - 58

Missing Motor Phase Function

[1] On

All set-ups

FALSE

-

Uint8

4 - 61

Jump Frequency From [Hz]

0 Hz

All set-ups

TRUE

-1

Uint16

4 - 63

Jump Frequency To [Hz]

0 Hz

All set-ups

TRUE

-1

Uint16

6.2.10 5-** Digital In/Out

Parameter
Number

Parameter Description

Default Value

2 Setup

Change During
Operation

Conver-

sion

Index

Type

5 - 10

Terminal 18 Digital Input

[8] Start

All set-ups

TRUE

-

Uint8

5 - 11

Terminal 19 Digital Input

[10] Reversing

All set-ups

TRUE

-

Uint8

5 - 12

Terminal 27 Digital Input

[1] Reset

All set-ups

TRUE

-

Uint8

5 - 13

Terminal 29 Digital Input

[14] Jog

All set-ups

TRUE

-

Uint8

5 - 15

Terminal 33 Digital Input

[16] Preset ref bit 0

All set-ups

TRUE

-

Uint8

5 - 40

Function Relay

[0] No operation

All set-ups

TRUE

-

Uint8

5 - 55

Terminal 33 Low Frequency

20 Hz

All set-ups

TRUE

0

Uint16

5 - 56

Terminal 33 High Frequency

5000 Hz

All set-ups

TRUE

0

Uint16

5 - 57

Terminal 33 Low Ref./Feedb. Value

0

All set-ups

TRUE

-3

Int32

5 - 58

Terminal 33 High Ref./Feedb. Value

50

All set-ups

TRUE

-3

Int32