8.2 Other Specifications

Protection and Features:

•

Electronic thermal motor protection against overload.

•

Temperature monitoring of the heatsink ensures that the frequency converter trips in case of overtemperature

•

The frequency converter is protected against short-circuits on motor terminals U, V, W.

•

If a motor phase is missing, the frequency trips and issues an alarm.

•

If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).

•

Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit voltage is too low or too high.

•

The frequency converter is protected against earth faults on motor terminals U, V, W.

Mains supply (L1/L, L2, L3/N):

Supply voltage

200-240 V ±10%

Supply voltage

380-480 V ±10%

Supply frequency

50/60 Hz

Max. imbalance temporary between mains phases

3.0 % of rated supply voltage

True Power Factor (λ)

≥ 0.4 nominal at rated load

Displacement Power Factor (cosφ) near unity

(> 0.98)

Switching on input supply L1/L, L2, L3/N (power-ups)

maximum 2 times/min.

Environment according to EN60664-1

overvoltage category III/pollution degree 2

The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 240/480 V maximum.

Motor output (U, V, W):

Output voltage

0 - 100% of supply voltage

Output frequency

0-200 Hz (Advanced Vector Control), 0-400 Hz (u/f)

Switching on output

Unlimited

Ramp times

0.05 - 3600 sec.

Cable lengths and cross sections:

Max. motor cable length, screened/armoured (EMC correct installation)

15 m

Max. motor cable length, unscreened/unarmoured

50 m

Max. cross section to motor, mains*
Connection to load sharing/brake (M1, M2, M3)

6.3 mm insulated Faston Plugs

Max. cross section to load sharing/brake (M4, M5)

16 mm

2

/6AWG

Maximum cross section to control terminals, rigid wire

1.5 mm

2

/16 AWG (2 x 0.75 mm

2

)

Maximum cross section to control terminals, flexible cable

1 mm

2

/18 AWG

Maximum cross section to control terminals, cable with enclosed core

0.5 mm

2

/20 AWG

Minimum cross section to control terminals

0.25 mm

2

* See tables for mains supply for more information!

Digital inputs (Pulse/enocder inputs):

Programmable digital inputs (Pulse/encoder)

5 (1)

Terminal number

18, 19, 27, 29, 33,

Logic

PNP or NPN

Voltage level

0 - 24 V DC

Voltage level, logic'0' PNP

< 5 V DC

Voltage level, logic'1' PNP

> 10 V DC

Voltage level, logic '0' NPN

> 19 V DC

Voltage level, logic '1' NPN

< 14 V DC

Maximum voltage on input

28 V DC

Input resistance, R

i

approx. 4 k

Max. pulse frequency at terminal 33

5000 Hz

Min. pulse frequency at terminal 33

20 Hz