Controller alarm led, Table 13-c: controller alarms – GE Industrial Solutions GPS 4812_24 User Manual

Page 100

Advertising
background image

Galaxy Power System 4812/24

13 - 6 Troubleshooting Millennium Systems

Issue 9 Januray 2008

Controller Alarm

LED

Table 13-C: Controller Alarms

(See Figures 12-2 and 12-3)

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Other

Indication(s)

Possible

Problem(s)

Possible Solution(s)

Controller

Major

Controller Fail

--

•BSH failure

•BSJ failure
•Option board

failure

•Display failure
•BIC failure

Check the BSH board to see
if the green LED is
extinguished and the yellow
LED is lit. If so, perform
the following steps:
1. Press the SW200 reset

switch on the top of the
BSH board. If all
diagnostics pass, it is
possible that some type
of “one time”
abnormality occurred to
cause the failure.

2. If the diagnostics did not

pass, or if the problem
recurs, unplug all the
optional circuit board
cables, then press the
reset switch on the top of
the BSH board again. If
all the diagnostics pass,
install optional circuit
board cables one at a
time, verifying operation
after each.

3. If the diagnostics did not

pass, Replace the BSH
board and verify the
failure is resolved. If so,
reinstall the optional
circuit boards and cables
one at a time.

4. If the problem is not

corrected, call technical
support.

Advertising