Specifications, Gps 4812/24, 9 specifications – GE Industrial Solutions GPS 4812_24 User Manual

Page 63: 9specifications

Advertising
background image

Galaxy Power System 4812/24

Issue 9 Preliminary Januray 2008

Specifications 9 - 1

9

Specifications

GPS 4812/24

Table 9-A: Galaxy Power System 4812/24 Specifications

Electrical
AC Input

Input Distribution

592A2

596D

• 125A circuit breaker per 2-shelf cabinet
• 150A circuit breaker per 3-shelf cabinet
• 25A circuit breaker per rectifier for individual feeds

• 110 / 125A circuit breaker per 1-shelf cabinet
• 2 x 110 / 125A circuit breaker per 2-shelf cabinet
• 2 x 150A circuit breaker per 3-shelf cabinet
• 50A circuit breaker per rectifier for individual feeds

Minimum Wire Size

596A2

596D

• 2 gauge/35 mm

2

- 1 and 2-shelf cabinet

• 1/0 gauge/50 mm

2

- 3-shelf cabinet

• 10 gauge/6 mm

2

- per rectifier for individual feeds

• 2 gauge/35 mm

2

- 1-shelf cabinet

• 2 x 2 gauge/35 mm

2

- 2-shelf cabinet

• 2 x 1/0 gauge/50 mm

2

- 3-shelf cabinet

• 8 gauge/10 mm

2

- per rectifier for individual feeds

Cabinet Output -48V

Full Height

Half Height

Output Current

596A2

596D

55 - 800A

110 - 1,600A

50 - 400A

110 - 800A

System Output -48V

2 x Full Height

1 Half Height + 1 Full Height

Maximum System

Output Current

596A2
596D


55 - 1,200A
110 - 3,200A


55 - 1,200A
110 - 2,400A


3,520A

1

7,040A

1

1. With Galaxy Millennium Controller

Advertising