Galaxy Power System 4812/24

9 - 6 Specifications

Issue 9 Preoiminary Januray 2008

Battery Connection Panels

Table 9-D: Battery Connection Panels

LVBD

Contactors

Shunt

Off-Line

Equalize

4

Fuse

Holder

Panel

Figure

H569-436

ED83141-31

2 x 500A

1000A

G30

G32

6-1

1,200A

1,500A

G31

G31

6-2

2 x NH3

1

G34

G41

6-3

NH3

1

G35

G42

6-4

800A

600A

G36H

G33

6-5

1,200A

3 x 1,000A

X

3 x US

2

G37F

G60

6-6

X

3 x US

2

G38F

G61

6-6

1,200A

2 x 600A

2 x NH3

1

G80

G31 + G43

6-7

1,200A

4 x 600A

4 x NH3

1

G81

G31 + 2 x G43

6-7

1,200A

6 x 600A

6 x NH3

1

G82

G31 + 3 x G43

6-7

600A

G84H

G34

6-8

1,000A

G85F

G35

6-9

6 positions for circuit breakers

3

G86

G63

6-10

800A 6 positions for circuit breakers

3

G87

G64

6-10

1. NH3 Fuse Holders accept DIN Fuses 315 to 630A
2. US Fuse Holders accept TPL-CZ fuses < 600A
3. 400A Circuit Breaker uses 2 positions
4. Off-Line Equalize panels use ES671 Off-line Equalize Converter to provide battery equalize voltage