Miscellaneous alarms, Table 14-f: miscellaneous alarms – GE Industrial Solutions GPS 4812_24 User Manual

Page 123

Advertising
background image

Galaxy Power System 4812/24

Issue 9 Januray 2008

Troubleshooting Vector Systems 14 - 11

Miscellaneous

Alarms

Table 14-F: Miscellaneous Alarms

Controller

Alarm

Status

Vector

Controller Display

Other

Indication(s)

Possible

Problem(s)

Possible Solution(s)

Major

BATT ON
DISCHRGE

Rectifiers
may say
ACF.

Temporary
condition that
may be
associated with
other alarms

Call technical support.

Major

AUXILIARY
INPUT

Auxiliary
equipment
may have
alarm.

Problem with
operation of
auxiliary
equipment

Call technical support.

Major

MAINTENANCE
OPEN

Red LED is
lit on control
panel.

Input Number 4
(MAINT) of the
BLJ3 terminal
connection
board is
interrupted.

Re-establish connection.

Major

SENSE VOLT
FAIL

Red LED is
lit on control
panel.

Broken
connection or
blown fuse.

Re-establish connection or replace blown
fuse.

Minor

load imbalance

Yellow LED
is lit on
control
panel.

A rectifier is
unable to load
share properly.

Identify rectifier that is not functioning
properly; reseat and retest. If rectifier still
does not load share, replace rectifier.

None

None

Red LED is
lit on some
battery
contactor
drive
boards,
while green
LED is lit on
others.

If a green LED
is lit despite a
contactor open
command
issued by the
controller, the
drive card or the
contactor has
failed.

Call technical support.

None

None

--

Fuse has
operated.

Replace fuse F2 (power) on the BLJ3
terminal board.