Rectifier related alarms, Table 14-e: rectifier related alarms – GE Industrial Solutions GPS 4812_24 User Manual

Page 120

Advertising
background image

Galaxy Power System 4812/24

14 - 8 Troubleshooting Vector Systems

Issue 9 Januray 2008

Rectifier Related

Alarms

Table 14-E: Rectifier Related Alarms

(See Figures 12-6 and 12-8)

Controller

Alarm

Status

Vector

Controller Display

Rectifier

LED

Rectifier

Display

Possible

Problem(s)

Possible Solution(s)

Major

RECT ID
CONFLICT

None

None

Rectifier ID
number has not
been set.

Set the rectifier ID using the
procedure in Section 11,
“Installing or Replacing a
Rectifier”.

Major

RECT ID
CONFLICT

None

None

Two or more
rectifiers have
the same ID
number.

See above.

Major

MULTI RECT

FAIL

ALM

None

More than one
rectifier has an
ALM LED lit.

See rectifier alarms listed below.

Major

MULTI RECT

FAIL

--

--

Loss of
communication
with controller:
•Defective

interface from
multiple
rectifiers to
controller

•Internal failure

of controller or
multiple
rectifiers

1. Verify that the controller is

powered and operating
correctly.

2. If there are no controller

alarms, replace rectifiers that
have lost communication.

3. If the problem is not solved,

call technical support.

Major

VERY HIGH

VOLTGE

ALM

HO

•Lightning has

struck system.

•Internal

rectifier failure

1. Toggle the ON/STBY switch

into the STBY position and
then back into the ON position.

2. If the problem is not corrected,

replace the rectifier.

Minor

RECTIFIER FAIL

Blinking
ALM LED
on rectifier

--

Loss of
communication
with controller:
•Defective

interface from
rectifier to
controller

•Internal

controller or
rectifier failure

1. Verify that the controller is

powered and operating
correctly.

2. If there are no controller

alarms, replace the rectifier.

3. If the problem is not corrected,

call technical support.