Galaxy Power System 4812/24

13 - 4 Troubleshooting Millennium Systems

Issue 9 Januray 2008

Battery Alarm LED

Table 13-B: Battery Alarms

(See Figure 12-7)

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Other

Indication(s)

Possible Problem(s)

Possible Solution(s)

Battery

Critical

Very Low Voltage

--

Occurs in an operating
system following an
extended commercial
ac power outage,
during which the
batteries are providing
power for the system
and the system voltage
is approaching the
user-defined low limit.

1. If commercial ac

power is present but
the system voltage
remains low, call
technical support.

2. Investigate other

alarms that may be
present
(rectifier-related
alarms and the AC Fail
alarm may also occur
during the fault
condition).

Battery*

*Alarm
must be
configured
to turn on
the Battery
LED; not a
factory
default.

Major

Contactor 1 Open

Red LED on
contactor
drive board is
lit.

Contactor is open:
•Open has been

initiated by controller.

•Open has been

initiated manually.

1. Follow instructions on

the label adjacent to
the contactor drive
board (see Figure
12-7).

2. If the problem is not

corrected, call
technical support.

Battery*

*Alarm
must be
configured
to turn on
the Battery
LED; not a
factory
default.

Major

Contactor 1 Fail

--

Contactor or drive
board has failed.

Call technical support.

Battery

Minor

Open String

Alarm LED
on battery
fuse panel is
lit.

Battery fuse has
operated or bat string
switch has opened..

Replace the operated
fuse.

Battery

Minor

Low Reserve Time --

Controller has
calculated that battery
reserve time is below
the alarm threshold
level.

Call technical support.