Connect DC Power

For DC powered models, you must supply your own power

cables and one Phillips screwdriver. DC power cables must

have a wire gauge of at least 16 AWG and a 72 VDC, 6A

rating. Remove the protective covers from the DC power

terminal blocks. Use the Phillips screwdriver to tighten the

connections.

Caution: Always connect the earth electrical grounds first,

and keep the earth grounds connected whenever you are

working on the device.

1. Connect a ground wire from the chassis ground to the rack.
2. Connect one end of another ground wire at the ground

connector at Power 1 on the device chassis. Then connect

the other end of the ground wire to the ground connection

at the DC power source.

3. Connect the negative (– 48VDC) side of a DC power cable

to the Power 1 terminal on the chassis, labeled with the

minus symbol (–), and connect the positive (0V) side of the

DC power cable to the Power 1 terminal labeled with the

plus symbol (+). The negative (minus symbol) terminal is

in the center, and the plus terminal is to the right.

4. Connect the other ends of the negative side and the

positive sides of the DC cable to the negative and positive

connectors of the power source.

5. If you want to connect to redundant power, repeat steps

2 and 3 for Power 2 and then connect the other ends to a

separate power source.

Caution: If possible, turn off the power to the power sources

while you are making the above connections.

Note: Be sure to connect the positive sides of the cables to

the positive sides of the power sources, and the negative

sides of the power cables to the negative sides of the power

sources. The two power LEDs on the front panel light up to

indicate that both power sources are on.

Quick Install Guide

Director xStream™

Data Monitoring Switch

Unpack and Inspect

Carefully unpack the Director xStream

TM

and retain materi-

als for later use. Check the packing slip against parts

received. If any part is missing or damaged, contact Net

Optics Customer Service. (Note: SFP and SFP+ modules

are ordered and shipped separately.)

The Director xStream product ships with the following:

• Director xStream software
• (1) xStream appliance
• (2) Power cords
• (1) Cable, 3 Meter, RJ45, CAT 5e 4-Pair
• (1) DB9 to RJ45 cable, 6 ft.
• Screws and washers for mounting the appliance
• Quick Install Guide (this document)
• (1) CD containing the xStream Family User Guide and

xStream Family CLI Command Reference

• Registration instructions
• Service Plan Reference Guide
• Extended Warranty, if purchased

Rack Mounting Director xStream

The Director xStream appliance is designed to mount in

a 19-inch rack, occupying 1U of height. Slide the chassis

into the rack and fasten it in place at the front panel ears

using the supplied screws and washers.

Ground the chassis to the rack by connecting a 14 AWG

minimum ground wire with a #8 ring lug to the ground con-

nection on the rear of the chassis. Terminate the other end

of the ground wire to the rack ground bus bar.

Connect AC Power

If you are installing the appliance with AC connectors:

1. Connect one of the AC power cords to one of the AC

power connectors on the rear panel.

2. Plug the other end of the cord into an AC power circuit.
3. For redundant power, connect the other AC power cord

to the other AC power connector on the rear panel.

4. Plug the other end of the cord into a different AC power

source.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

Console

Management

24 Network/Monitor Ports

Activity LED

Activity LED

Link LED

Console Port

Management

Port

© 2013 by Net Optics, Inc. Net Optics® is a registered trademark of Net Optics, Inc. Director xStream

TM

is a trademark of Net Optics, Inc.

800-0136-002 Rev F PUBDIRXQ 06/13

P

w

r

1

P

w

r

2

Return

Ground

-48VDC

Return

Ground

-48VDC

Chassis

Ground