Net Optics iLink Agg xStream User Manual

Quick install guide ilink agg xstream, Ilink agg, Rack mounting ilink agg xstream

Advertising
background image

Connect DC Power

For DC powered models, you must supply your own power

cables and one Phillips screwdriver. DC power cables must

have a wire gauge of at least 16 AWG and a 72 VDC, 6A rating.

Remove the protective covers from the DC power terminal

blocks. Use the Phillips screwdriver to tighten the connections.

Caution: Always connect the earth electrical grounds first, and

keep the earth grounds connected whenever you are working

on the device.

1. Connect a ground wire from the chassis ground to the rack.

2. Connect one end of another ground wire at the ground

connector at Power 1 on the device chassis. Then connect

the other end of the ground wire to the ground connection at

the DC power source.

3. Connect the negative (– 48VDC) side of a DC power cable

to the Power 1 terminal on the chassis, labeled with the

minus symbol (–), and connect the positive (0V) side of the

DC power cable to the Power 1 terminal labeled with the

plus symbol (+). The negative (minus symbol) terminal is in

the center, and the plus terminal is to the right.

4. Connect the other ends of the negative side and the

positive sides of the DC cable to the negative and positive

connectors of the power source.

5. If you want to connect to redundant power, repeat steps

2 and 3 for Power 2 and then connect the other ends to a

separate power source.

Caution: If possible, turn off the power to the power sources

while you are making the above connections.

Note: Be sure to connect the positive sides of the cables to the

positive sides of the power sources, and the negative sides of

the power cables to the negative sides of the power sources.

The two power LEDs on the front panel light up to indicate that

both power sources are on.

Quick Install Guide

iLink Agg xStream™

Unpacking and Inspection

Carefully unpack iLink Agg xStream and retain materials for later

use. Check the packing slip against parts received. If any part

is missing or damaged, contact Net Optics Customer Service.

(Note: SFP and SFP+ modules are ordered and shipped

separately.)

iLink Agg xStream product ships with the following:

• iLink Agg xStream software
• (1) xStream device
• (2) Power cords
• (1) Cable, 3 Meter, RJ45, CAT 5e 4-Pair
• (1) DB9 to RJ45 cable, 6 ft.
• Screws and washers for mounting the device
• iLink Agg xStream Quick Install Guide (this document)
• (1) CD containing the xStream Family User Guide and

xStream Family CLI Reference

• Registration instructions
• Service Plan Reference Guide
• Extended Warranty, if purchased

Rack Mounting iLink Agg xStream

iLink Agg xStream is designed to mount in a 19-inch rack,

occupying 1U of height. Slide the chassis into the rack and

fasten it in place at the front panel ears using the supplied

screws and washers.

Ground the chassis to the rack by connecting a 14 AWG ground

wire with a #8 ring lug to the ground connection on the rear of

the chassis. Terminate the other end of the ground wire to the

rack ground bus bar.

Connect AC Power

If you are installing the appliance with AC connectors:

1. Connect one of the AC power cords to one of the AC power

connectors on the rear panel.

2. Plug the other end of the cord into an AC power circuit.

3. For redundant power, connect the other AC power cord to the

other AC power connector on the rear panel.

4. Plug the other end of the cord into a different AC power

source.

© 2013 by Net Optics, Inc. Net Optics® is a registered trademark of Net Optics, Inc. iLink Agg xStream

TM

is a trademark of Net Optics, Inc.

800-0137-002 Rev E PUBLAXQ 06/13

iLink Agg

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

Console

Management

24 Network/Monitor Ports

Activity LED

Activity LED

Link LED

Console Port

Management

Port

P

w

r

1

P

w

r

2

Return

Ground

-48VDC

Return

Ground

-48VDC

Chassis

Ground

Advertising