AUXILIARY SETUP

Tap [Auxiliary Setup] from the Setup menu. Some

These screens allow you to setup and configure
any auxiliary equipment. Check any auxiliary
equipment that needs to be set up.

Each enabled item requires an IP address to
communicate to the PLC using the Modbus
protocol, which can be entered by double clicking
on the IP address field.

Default IP addresses can be found in Appendix E.

Note: Pace 5.0+ supports integrated auximilary
equipment. Setting the IP address of the auxiliary
equipment to the same as the main PLC enables
the integrated auxiliary device.

ALS Setup
In this screen, Flush Times and Flow Rates may be
edited.

Time until Flush (sec): Time period between
flushes.

Duration of Flush (sec): Time duration for the
flush.

Flow Start Cleaning (GPM): Flow rate when flush
starts.

Flow Stop Cleaning (GPM): Flow rate when flush
stops.

Tap [Next] to move to the next Auxiliary Setup
screen

Figure 35: ALS Setup

Lake Level Controls Setup
This screen allows you to configure all aspects of
Lake fill, transfer pump and timed pump operation
when using an integrated lake level control system.

Figure 36: Lake Level Controls Setup

Up to 8 Well/Transfer/Timed pumps can be
controlled when using the integrated system. Set
the IP address of the lake Level Controls auxiliary
equipment to match the main PLC to enable the
integrated controls (Note: The IO mapping must be
configured for the Lakefill/Transfer/Timed pumps to
use the integrated system, consult the factory when
adding equipment to 5.0+ Pace systems).

The master Auto button must be enabled for any of
the level/timed pumps to run. Press “System Off” to
disable all Level/Timed pumps. (Pump station
operation is not affected).

Touch the pump name to configure the pump.

Figure 37: Level/Timed pump configuration

Set the pump name by touching the Name field for
the pump you are configuring. This is the “Source”.

Pumps may be configured in “Groups”. When the
first pumps level (or level/time combination) calls for
the pump to run, all pumps in the group will be
evaluated to determine which will run, based on run
hours and switch settings.

Timed pump can be configured with or without level
control. A timed pump will be enabled to run on the
days specified, after the start time and for the
duration specified. If also level controlled, then the