Figure 39: Lake Level Controls Setup

Timed Pump Setup (Non-Integrated only)
This screen allows you to enable the timed pump
setup. If the ‘Feedback Enable’ box is checked, the
pump will send feedback to the PLC.

Enable the checkboxes for each day that a pump
needs to be timed. For each day enabled, enter the
start time and duration in a pop up screen.

Tap [Next] to move to the next Auxiliary Setup
screen.

Figure 40: Timed Pump Setup

Simple Filters Setup
This screen allows you to setup the simple or Wye
filters.

∆P Present (sec) is the time between flushes when
differential pressure is on, or when the analog
differential pressure is less than the differential
setpoint. Check the ‘Wye’ checkbox to enable a
Wye filter, (which doesn’t use ∆P) and enter values
in editable fields.

Simple Filters Setup
This screen allows you to setup the simple or Wye
filters.

∆P Present (sec) is the time between flushes when
differential pressure is on, or when the analog
differential pressure is less than the differential
setpoint. Check the ‘Wye’ checkbox to enable a
Wye filter, (which doesn’t use ∆P) and enter values
in editable fields.

Tap [Next] to move to the next Auxiliary Setup
screen.

Figure 41: Simple Filters Setup

Scanners Filter Setup
The Scanners Filter setup screen is similar to
Simple Filters setup, but it does not have the Wye
filter option.

Select the filter from the drop down menu and enter
values in the editable fields as needed.

Tap [Next] to move to the next Auxiliary Setup
screen.

Figure 42: Scanners Filter Setup

VFD Bypass
Tap [VFD Bypass] from the Options Setup Menu.

This screen allows you to enable or disable bypass
for desired VFDs using the radio buttons.

Tap [Close] to return to the Options Setup Menu.