Sensors, Thermal contacts) + ld, Thermal contacts ld disconnected – Xylem GK GV (8204, 8204X) User Manual

Page 30: Control subcab 4gx/7g subcab awg h07rn-f

Advertising
background image

Sensors connection

WS004611B

SENSORS

Color and marking of control leads

*IF Y/D-start, sensors not connected

Control

SUBCAB 4GX/7G SUBCAB AWG

H07RN-F*

T1

WH T1

OG

BK 4

T2

WH T2

BU

BK 5

(Thermal Contacts) + LD

LD

TC

Max 12 V

WH/YE

T1 Control leads

T1/*OG/1

+7

SMR311

SMR311

BN

T2

WH/YE

T2/*BU/2

-5

BN

T15

**T3

*SUBCAB AWG

**T4

*Screened SUBCAB

Thermal Contacts LD Disconnected

LD

TC

Max 12 V

WH/YE

T1 Control leads

T1/*OG/1

+7

BN

T2

T2/*BU/2

-5

WH/YE

T15

BN

**T3

*SUBCAB AWG

**T4

*Screened SUBCAB

Sensor connection characteristics

The values have a 10 % tolerance.

Sensors

Value (mA)

Definition

LD and thermal contact

0

Overtemperature

7.8

OK

36

Leakage

Installation

28

GK, GV (8204, 8204X) Installation, Operation, and Maintenance Manual

Advertising