Sensors, Thermal contacts) + ld, Thermal contacts ld disconnected – Xylem GK GV (8204, 8204X) User Manual
Page 30: Control subcab 4gx/7g subcab awg h07rn-f
Advertising
![background image](/manuals/310389/30/background.png)
Sensors connection
WS004611B
SENSORS
Color and marking of control leads
*IF Y/D-start, sensors not connected
Control
SUBCAB 4GX/7G SUBCAB AWG
H07RN-F*
T1
WH T1
OG
BK 4
T2
WH T2
BU
BK 5
(Thermal Contacts) + LD
LD
TC
Max 12 V
WH/YE
T1 Control leads
T1/*OG/1
+7
SMR311
SMR311
BN
T2
WH/YE
T2/*BU/2
-5
BN
T15
**T3
*SUBCAB AWG
**T4
*Screened SUBCAB
Thermal Contacts LD Disconnected
LD
TC
Max 12 V
WH/YE
T1 Control leads
T1/*OG/1
+7
BN
T2
T2/*BU/2
-5
WH/YE
T15
BN
**T3
*SUBCAB AWG
**T4
*Screened SUBCAB
Sensor connection characteristics
The values have a 10 % tolerance.
Sensors
Value (mA)
Definition
LD and thermal contact
0
Overtemperature
7.8
OK
36
Leakage
Installation
28
GK, GV (8204, 8204X) Installation, Operation, and Maintenance Manual
Advertising