Centripro, Commercial water systems – Xylem IM192R00 FloStandard SIMPLEX PUMP CONTROL PANEL User Manual

Page 10

Advertising
background image

10

ITT

CENTRIPRO

Commercial Water Systems

Units supplied with Class 10 Overload Protection with

Pump Monitor () and Lightning Protection

NEMA

Max. Fuse

Order

Max. Input

Starter

Max.

holder

Enclosure

Weight

Number

HP Voltage

Size

Amps

Size

Size

lbs.

(Amps)

FV2070027A1W 7½

1

27

30

36”H x 16”W x 9”D

40

FV2015045A2W

15

2

45

60

55

FV2030090A3W

30

230

3

90

100

45”H x 20”W x 11”D

111

FV2050130A4W

50

4

135

150

170

FV2100311A5W 100

5

270

400

73”H x 22”W x 18”D

440

FV4010018B1W

10

1

27

30

36”H x 16”W x 9”D

40

FV4025045B2W

25

2

45

60

55

FV4050090B3W

50

460

3

90

100

45”H x 20”W x 11”D

111

FV4100200B4W 100

4

135

200

170

FV4200311B5W 200

5

270

400

73”H x 22”W x 18”D

440

‡Class J fuses are not supplied.

Accessories sold separately. Field installation required.

FloStandard™ Simplex Pump Control Panels

J

Note: Recommended class “R” Fuse Type, dual element, time delay (not Included).

Option

Description

Weight (Lbs)

FSCT

120 V Control Transformer

7

FSSP

Surge/Lightning Protection

FSPP

Pump Monitor (777) Includes class 10 overload

2

FSTC

Time Clock

FSPH

Condensation Header

FSGN

Green Run Light

1

FSRN

Red Alarm Light

FSOP

Class 10 Overload Protection

†Requires control transformer option FSCT. For specials or other options, consult factory.

Advertising