Centripro, Commercial water systems – Xylem IM192R00 FloStandard SIMPLEX PUMP CONTROL PANEL User Manual
Page 14
![background image](/manuals/310475/14/background.png)
1
ITT
CENTRIPRO
Commercial Water Systems
CT Size Chart
(CTs must be installed in the field for selected HP)
Size 1 0VAC
HP
FLA
Fuse Size
Number of
Number of Conductors
Loops
through A, B & C
‡
5 HP
7.6 FLA
FRSR15
3
4
7.5 HP
11FLA
FRSR20
2
3
10 HP
14FLA
FRSR20
1
2
‡ The number of loops may differ from the number of conductors through the current transformers.
Always double check based on HP and FLA.
Size 0VAC
HP
FLA
Fuse Size
Number of
Number of Conductors
Loops
through A, B & C
‡
10 HP
28FLA
FRNR40
0
1
15 HP
42FLA
FRSR250
0
1
‡ The number of loops may differ from the number of conductors through the current transformers.
Always double check based on HP and FLA.
Size 0VAC
HP
FLA
Fuse Size
Number of
Number of Conductors
Loops
through A, B & C
‡
15 HP
21FLA
FRSR35
1
2
20 HP
27FLA
FRSR40
0
1
25 HP
34FLA
FRSR50
0
1
‡ The number of loops may differ from the number of conductors through the current transformers.
Always double check based on HP and FLA.