Centripro, Commercial water systems – Xylem IM192R00 FloStandard SIMPLEX PUMP CONTROL PANEL User Manual

Page 14

Advertising
background image

1

ITT

CENTRIPRO

Commercial Water Systems

CT Size Chart

(CTs must be installed in the field for selected HP)

Size 1 0VAC

HP

FLA

Fuse Size

Number of

Number of Conductors

Loops

through A, B & C

5 HP

7.6 FLA

FRSR15

3

4

7.5 HP

11FLA

FRSR20

2

3

10 HP

14FLA

FRSR20

1

2

‡ The number of loops may differ from the number of conductors through the current transformers.

Always double check based on HP and FLA.

Size  0VAC

HP

FLA

Fuse Size

Number of

Number of Conductors

Loops

through A, B & C

10 HP

28FLA

FRNR40

0

1

15 HP

42FLA

FRSR250

0

1

‡ The number of loops may differ from the number of conductors through the current transformers.

Always double check based on HP and FLA.

Size  0VAC

HP

FLA

Fuse Size

Number of

Number of Conductors

Loops

through A, B & C

15 HP

21FLA

FRSR35

1

2

20 HP

27FLA

FRSR40

0

1

25 HP

34FLA

FRSR50

0

1

‡ The number of loops may differ from the number of conductors through the current transformers.

Always double check based on HP and FLA.