Centripro, Commercial water systems – Xylem IM192R00 FloStandard SIMPLEX PUMP CONTROL PANEL User Manual

Page 11

Advertising
background image

11

ITT

CENTRIPRO

Commercial Water Systems

sUggEsTEd FUsE, WIRE aNd CONdUIT sIzEs

0 Volt

HP Fuse Wire Conduit

3

17.5

14

0.50

5

30

10

0.50

40

8

0.75

10

50

8

0.75

15

80

6

1.00

20

100

4

1.00

25

125

3

1.25

30

150

2

1.25

30 Volt

HP Fuse Wire Conduit

3

15

14

0.50

5

25

12

0.50

35

10

0.50

10

45

8

0.75

15

70

6

1.00

20

90

4

1.00

25

110

4

1.00

30

125

3

1.25

0 Volt

HP Fuse Wire Conduit

5

12

14

0.50

7½ 17.5

14

0.50

10

25

12

0.50

15

35

10

0.50

20

45

8

0.75

25

60

8

0.75

30

70

6

1.00

40

90

6

1.00

50

110

4

1.00

60

125

3

1.25

NOTE:
Fuses are for main disconnect. Recommended dual element, time-delay type fuse.
Wire is copper, type “THW,” 75º C.
All sizes are recommended only and are not a substitute for hiring a local electrician to properly size

according to NEC and local codes.

Advertising