Centripro, Commercial water systems – Xylem IM192R00 FloStandard SIMPLEX PUMP CONTROL PANEL User Manual
Page 19
Advertising
1
ITT
CENTRIPRO
Commercial Water Systems
CT Size Chart
(CTs must be installed in the field for selected HP)
Size 0VAC
HP
FLA
Fuse Size
CT Size
Number of
Number of Conductors
Loops
through A, B & C
‡
60 HP
77FLA
FRSR100
No CT
0
1
75 HP
96FLA
FRSR150
100:5
4
5
100 HP 124FLA
FRSR170
150:5
4
5
‡ The number of loops may differ from the number of conductors through the current transformers.
Always double check based on HP and FLA.
Size 0VAC
HP
FLA
Fuse Size
CT Size
Number of
Number of Conductors
Loops
through A, B & C
‡
50 HP 130FLA
FRNR200
150:5
4
5
‡ The number of loops may differ from the number of conductors through the current transformers.
Always double check based on HP and FLA.
Advertising