CT Size Chart

(CTs must be installed in the field for selected HP)

Size  0VAC

HP

FLA

Fuse Size

CT Size

Number of

Number of Conductors

Loops

through A, B & C

60 HP

77FLA

FRSR100

No CT

0

1

75 HP

96FLA

FRSR150

100:5

4

5

100 HP 124FLA

FRSR170

150:5

4

5

‡ The number of loops may differ from the number of conductors through the current transformers.

Always double check based on HP and FLA.

Size  0VAC

HP

FLA

Fuse Size

CT Size

Number of

Number of Conductors

Loops

through A, B & C

50 HP 130FLA

FRNR200

150:5

4

5

‡ The number of loops may differ from the number of conductors through the current transformers.

Always double check based on HP and FLA.