Centripro, Commercial water systems – Xylem IM192R00 FloStandard SIMPLEX PUMP CONTROL PANEL User Manual
Page 16
Advertising
![background image](/manuals/310475/16/background.png)
1
ITT
CENTRIPRO
Commercial Water Systems
CT Size Chart
(CTs must be installed in the field for selected HP)
Size 3 0VAC
HP
FLA
Fuse Size
Number of
Number of Conductors
Loops
through A, B & C
‡
25 HP
68FLA
FRNR100
0
1
30 HP
80FLA
FRNR150
0
1
‡ The number of loops may differ from the number of conductors through the current transformers.
Always double check based on HP and FLA.
Size 3 0VAC
HP
FLA
Fuse Size
Number of
Number of Conductors
Loops
through A, B & C
‡
30 HP
40FLA
FRSR60
0
1
40 HP
52FLA
FRSR80
0
1
50 HP
65FLA
FRSR100
0
51
‡ The number of loops may differ from the number of conductors through the current transformers.
Always double check based on HP and FLA.