Centripro, Commercial water systems – Xylem IM192R00 FloStandard SIMPLEX PUMP CONTROL PANEL User Manual

Page 16

Advertising
background image

1

ITT

CENTRIPRO

Commercial Water Systems

CT Size Chart

(CTs must be installed in the field for selected HP)

Size 3 0VAC

HP

FLA

Fuse Size

Number of

Number of Conductors

Loops

through A, B & C

25 HP

68FLA

FRNR100

0

1

30 HP

80FLA

FRNR150

0

1

‡ The number of loops may differ from the number of conductors through the current transformers.

Always double check based on HP and FLA.

Size 3 0VAC

HP

FLA

Fuse Size

Number of

Number of Conductors

Loops

through A, B & C

30 HP

40FLA

FRSR60

0

1

40 HP

52FLA

FRSR80

0

1

50 HP

65FLA

FRSR100

0

51

‡ The number of loops may differ from the number of conductors through the current transformers.

Always double check based on HP and FLA.