loss of phase/phase Imbalance: The overload

relay has phase loss and phase imbalance monitor-
ing circuitry. Loss of phase or a phase imbalance
of 25% or more of the average of the three phases
will result in a trip. Disconnect the unit from the
main power supply, find and correct cause for
phase loss of phase imbalance. Possible causes
would be blown fuse(s) or loose wiring connec-
tions. Reset the overload relay with the reset bar
on the front of the combination starter. Restart the

pump.

CONTROllER FUNCTIONs

FloStandard is designed to accept a variety of

inputs to function as a pump controller. Pressure
Switches, Level Sensors, Flow Switches, etc. can
be used as a dry contact signal to automatically
start and stop the pump. Caution should be used
to prevent pump cycling when utilizing remote
controllers.

sPECIFICaTIONs

gENERAl SpECIFICATIONS:

Enclosure Type

NEMA 3R Suitable for

Outdoor Use

Operating Temperature 4º F to 122º F

Storage Temperature

20º F to 149º F

Humidity

0-95% non-condensing

ElECTRICAl:

Voltage Input

+/- 10% Rated Panel

Voltage

Input Line Frequency

50/60 Hz +/- 2 Hz

Line Voltage / 115 Volts

Control Voltage

AC with control power

transformer option

Overload Capacity

125% of rated RMS

current for 60 seconds

Overload Class

10 or 20

Adjustable setting for

Time Overload

125% of rated motor

current

Agency Listing

UL508A or equivalent