Centripro, Commercial water systems – Xylem IM192R00 FloStandard SIMPLEX PUMP CONTROL PANEL User Manual
Page 21
Advertising
![background image](/manuals/310475/21/background.png)
1
ITT
CENTRIPRO
Commercial Water Systems
CT Size Chart
(CTs must be installed in the field for selected HP)
Size 0VAC
HP
FLA
Fuse Size
CT Size
Number of
Number of Conductors
Loops
through A, B & C
‡
125 HP 156FLA
FRSR200
150:5
4
5
150 HP 180FLA
FRSR250
200:5
4
5
200 HP 240FLA
FRSR350
300:5
4
5
‡ The number of loops may differ from the number of conductors through the current transformers.
Always double check based on HP and FLA.
Size 0VAC
HP
FLA
Fuse Size
CT Size
Number of
Number of Conductors
Loops
through A, B & C
‡
75 HP 193FLA
FRNR300
200:5
4
5
100 HP 248FLA
FRNR350
300:5
4
5
‡ The number of loops may differ from the number of conductors through the current transformers.
Always double check based on HP and FLA.
Advertising