1 Notes

The installation and operating instructions in this manual must be followed when installing and operating the TP1

condensate pump. Please read them carefully. We recommend that you keep it close to the pump. Particular

attention must be paid to notes marked as follows:

If this instruction is not followed, personal safety risks could ensue.

If this instruction is not followed, the device may not function properly and could be

damaged.

Other relevant regulations must also be observed, e.g. accident prevention regulations or internal operating

and safety instructions of the system manufacturer. Failure to follow these instructions can result in the loss

of all entitlement to claim damages.

TP1 condensate pump installation and operating instructions

GB

2 Included items (See Figure 2 Page 2)

4 Dimensions (See Figure 4 Page 2)

6 Curve

7 Installation sequence

5 Specifications

Supply voltage

100 - 240 V

Frequency

50 / 60 Hz

P1 power supply capacity

20 Watt

Current consumption

0.2 – 0.1 A

Degree of protection

IP 44 / Class F

Max. delivery head

45 kPa

Max. pump capacity

450 l/h

Noise level (L

w

)

46 dB(A)

Acid resistance

pH 2 or higher

Max. media temperature

+ 60° C

Min. ambient temperature

Not freezing

Floating contact

Break contact, switching capacity 250 VA

Tank volume

0.7 l (usable volume 0.5 l)

Packaging dimensions

215x215x180 mm

Packaging weight

1.6 kg

Subject to technical changes due to product modifications

WARNING

!

3 General description

The TP1 condensate pump is an automatic pump for pumping condensation water from condensing boilers, air

conditioning systems, coolers, dehumidifiers or other similar systems. The corresponding regulations on draining

to the sewage system must be observed. If necessary, a neutralising unit must be installed upstream.

Combustible liquids may not be pumped!

The condensate pump may not be run dry, as this can destroy the bearings in a very

short period.

WARNING

!

8 Installation

The TP1 condensate pump must be installed in dry rooms (frostproof and where the air temperature does

not exceed 60° C) using the installation bracket provided. It is mounted to the wall below the condensate

supply outlet. Ensure that the is mounted horizontally. If floor-mounted, ensure that it is in a stable position

We recommend that you also secure it to the nearest wall.

The unit may not be installed in areas where there is a danger of explosion!

!