10 Operating lamps / Overview of faults / Warranty

Work on electrical parts of the TP1 condensate pump may only be performed by qualified staff!

Ready for operation = Steady green light;

Fault

= Red light;

Pump running

= Flashing green light

The alarm output is opened when a fault occurs.

Operating lamp

Cause

Solution

Green

Red

Off

Off

Mains plug not plugged in

Insert plug

Power failure

Check mains and fuse;

Flashing Flashing Dry-run

Pump restarts automatically

(Poss. air in pump)

after one minute;

On

Flashing Pump blocked

Visual inspection of the pump

inlet in the tank and removal or

rinsing of dirt or foreign bodies;

On

On

Level exceeds alarm level

Pressure hose / non-return valve blocked

(clean or remove kink if applicable);

Off

Flashing Pump blocked and

Visual inspection of the pump inlet

Alarm level exceeded

in the tank and removal or rinsing of dirt

or foreign bodies;

Condensate from condensing systems is aggressive. Avoid contact with residual condensate in the

tank, in the condensate supply hose or in the pressure hose! Malfunctioning condensate pumps can be

returned to the manufacturer’s address. The manufacturer will refuse to accept packages with unpaid shipping

or invoices for repair.

The manufacturer guarantees the TP1 condensate pump for two years subject to correct installation and

proper use of the device.

11 Disposal

This product and parts thereof must be disposed of in an environmentally friendly way. Corresponding local

regulations must be observed.

12 CE conformity declaration

The TP1 condensate pump complies with the following European standards:

EN 60 335-1 + EN 60 335-2-51 (Safety of electrical systems)

EN 55 014-1 + EN 55 014-2 (Electromagnetic compatibility)

TP1 condensate pump installation and operating instructions

GB

!

!

13 Exploded view

1 Condensate inlet (ø 24 mm)

2 Additional inlet opening

(ø 24 mm) with plug

3 Magnet float

4 Mounting bracket

(for rear wall or left side wall)

5 Clip

6 Mains cable (2.0 m) with shock-proof plug

7 Alarm connection cable (floating, 2 m)

8 Non-contact electronic

fill level detection with echo sensors

9 Connection for pressure hose (14x2 mm, 6 m)

10 Non-return valve with bayonet Connection

11 Opening for non-return valve

12 Pressure nozzle

13 Tank (0.7 l; usable volume 0.5 l)

14 Permanent magnetic rotor / impeller

15 Pump sump

16 Operating LEDs

17 Stator of the high-efficiency spherical motor

pump