Technical data

MIQ/IC2

7 - 2

ba76034e01

01/2012

Current inputs

Feed-in

(power supply/isolator)

Measuring channels

2
Physically separated from the
IQ S

ENSOR

N

ET

Physical input current
range

0.0 ... 22.5 mA
If this range is exceeded, the input switches
itself off for approx. one minute as a protec-
tive measure

Allowed signal ranges

0 ... 20 mA: 0.0 mA

I

20.2 mA

4 ... 20 mA: 3.8 mA

I

20.2 mA

Undefined signal ranges
Display of OFL
(range within the physi-
cal input current range
but outside of the al-
lowed signal range)

At the lower end of the signal range
(with signal range 4 ... 20mA only):
I

Error threshold

< I < 3.8 mA

At the upper end of the signal range
(with signal range 0/4 ... 20mA only):
20.2 mA < I < I

Error threshold

Error signal ranges
Display of "----"
(corresponding to
setting of Error detec-
tion
)

Error detection <= Error threshold:
0.0 mA

I

I

Error threshold

Error detection >= Error threshold:
I

Error threshold

I

22.5 mA

Allowed common-mode
difference between the
measuring channels

10 VDC, 20 VAC

P-P

Measuring uncertainty
(precision)

< 0.2 % of the measured value ± 0.01 mA

Load

max. 250 Ohm

Electrical data

20.5 - 24 V
Output current max. 240 mA,
permanently short-circuit proof

Requirement or monitor-
ing of the supply voltage

(only applies if a power
supply/isolator is con-
nected)

21.5 ... 24 V
different from the IQ S

ENSOR

N

ET

voltage

monitoring (see system operating manual)
The voltage monitoring values are automat-
ically changed when a power supply/isolator
is connected.