Interface for the PROFIBUS

MIQ/(A-)PR

14

ba76020e01

01/2012

(B)

Connecting the

MIQ/(A-)PR component

at the

PROFIBUS with a loop-

through

To loop the PROFIBUS cable through the MIQ/(A-)PR component, a
shielding terminal is included in the scope of delivery.

Fig. 3-7

Shielding terminal with PROFIBUS cable and shield connection cable

1

Screw

2

Washer

3

Insulating part of the shielding terminal

4

Cable insulation of the PROFIBUS cable

5

Shielding braid of the PROFIBUS cable

6

Wires of the PROFIBUS cable

7

Shield connection wire

1

Carefully strip the cable insulation of both PROFIBUS cables
for approx. 35 mm.

2

Shorten the exposed shielding braid to approx. 15 mm.

3

Bare the PROFIBUS wires for approx. 5 mm.

4

Feed both cables through the free cable glands into the
module housing of the MIQ/(A-)PR.

5

Create a shield connection wire (7). To do so, strip a wire on
both ends for approx. 5 mm and 10 mm.

6

Insert a washer in the insulating part (3) of the shielding
terminal.

7

Feed both PROFIBUS cables into the insulating part (3) and
lead them through the insulating part.

8

Feed the long stripped end of the shield connection wire (7)
into the insulating part (3) of the shielding terminal.

1

2

5

7

4

3

6