Interface for the PROFIBUS

MIQ/(A-)PR

20

ba76020e01

01/2012

3.5

PROFIBUS checklist

The following checklist supports you when planning, projecting and
installing a PROFIBUS plant with the IQ S

ENSOR

N

ET

. For smooth

operation, you should be able to answer all questions with "Yes".

 Is the [bus system] (bus segment) installed without branch lines?

 Was the correct PROFIBUS cable used (cord type A according to

EN 50170)?

 Are the poles of the signal lines A line and B line correctly connected

at all bus connections?

 Is it guaranteed that there is no short-circuit between A line, B line

and cable shielding?

 Is the shielding installed free of interruptions?

 Are the guidelines for shielding and grounding being observed, and

doesn't any unallowed potential equalization current flow
via the shielding?

 Is the maximum cable length (per bus segment) observed for the

corresponding baud rate?

 Do all devices support the required baud rate?

 With 12 Mbit/s transmission rate only: Are the bus plugs suitable for

this baud rate?

 Are exactly two terminators switched on at the ends of the [bus

system] (bus segment)?

 Are the terminators supplied with voltage so the following applies:

U

B line

- U

A line

> + 500 mV?

 Do all devices have individual bus addresses?

 After changing the bus address, have the devices been restarted

(switched off and on again)?

 Do the addresses projected in the master correspond to the actual

addresses? Are all addresses less than or equal to the parameter
HSA and less than 126 (HSA = Highest Station Address)?

 Is the currently valid GSD being used? If you are in doubt, download

it from the Internet.

 Have admissible bus parameters been set only? If you are in doubt

set them to default values.