Interface for the PROFIBUS

MIQ/(A-)PR

16

ba76020e01

01/2012

Note
Using a shielding terminal, connect the shield of the PROFIBUS cable
to the potential equalization or grounding system of the plant in the
vicinity but outside of the MIQ module housing.

3.2.3

Rotary address switches

Fig. 3-10 Rotary address switches

A prerequisite for the configuration of the AnyBus-S module for
PROFIBUS
DP is the setting of its address. The address is set using
two rotary switches. The left-hand switch is used to set the tens digit,
whereas the right switch is used to set the ones digit of the address.
This enables addresses of 1-99 to be set.

Example

To set an address of 64:
Turn the left-hand switch to 6,
turn the right-hand switch to 4.

Note
The address cannot be changed during operation. A change of the
address becomes only effective after the address setting was changed
and the system was reset (see system operating manual).

14

Check and if necessary correct the position of the PROFIBUS
terminator switch.
The switch must be in the OFF position.

15

Perform the check:
 Check whether the wires and cables are screwed on tightly.
 Insulate open wires.
 Remove any cable remains from the MIQ/(A-)PR module.

16

Close the MIQ/(A-)PR module.