Chem-pro, Series operation, Paddlewheel sensor signal input wiring – Xylem C3V CHEMICAL METERING PUMPS User Manual

Page 10: 0 c3v external input/output signal connection

Advertising
background image

Page 10

Page 11

C3

C3

Stop and
Start the pump

Decrease
output speed

Increase
output speed

C3F

Series Operation

The C3F is a powerful yet simple to
operate metering pump.

Blue-White Industries

Made in the USA

tm

CHEM-PRO

Diaphragm
Failure
Detection

C3F | Diaphragm Metering Pump

NEMA 4X

IP66

To start the pump, press the
Start / Stop button

To increase the output, press
the Up button

To decrease the output, press
the Down button

To stop the pump, press the
Start / Stop button

To prime the pump, press the Up button and the Start / Stop
button at the same time. The pump will run in prime mode for
60 seconds at 100% output.

To stop primming before the 60 seconds, press the Start / Stop
button.

+

Series

6.1 How To Operate The C3F

Priming the C3F

SIGNAL INPUT/OUTPUT WIRE COLOR CODES

WIRE COLOR CODE

INPUT TYPE

MOTOR ON SIGNAL

5-20V DC open collector output
closed while motor is energized

FLOW VERIFICATION SENSOR (FVS)

ALARM RELAY

connect 2-conductor plug to either

normally open (NO) (factory default)

or normally closed (NC) side of receptacle.

3 AMP MAX @ 125VAC (24VDC)

BROWN (+) & BLACK (-)

PURPLE & PURPLE

WHITE (+) & BLACK (-)

BLUE (+) (non-powered) & BLACK (-)

ORANGE (+) (non-powered) & BLACK (-)

RED/WHITE (+ 20VDC)

BLACK (-)

YELLOW (signal)

CONTACT (10v @ 2 mA max)

HALL EFFECT, NPN

RED (+) & WHITE (-)

PADDLEWHEEL SENSOR SIGNAL INPUT WIRING

PADDLEWHEEL SENSOR

WIRE COLOR CODE

BLUE-WHITE

PADDLEWHEEL

SENSOR TYPE

MODEL FH

HALL EFFECT SENSOR

BLACK (-)

RED (+)

PUMP INPUT

WIRE COLOR CODE

MODEL FC

AC SINE WAVE SENSOR

BARE (signal)

BLACK (-)

RED (+ 20VDC)

WHITE (signal)

BLACK (-)

RED (+)

BLACK (-)

WHITE (+)

4-20 mA

0-10 VDC

AC sine wave, TTL, CMOS

7.0 C3V External Input/Output Signal Connection

C3V will accept a variety of external control input signals: 4-20mA, 0-10VDC,
TTL, CMOS, AC Sine waves, contact closures, Hall Effect, NPN. The 4-20mA
and 0-10 VDC loops must be powered. Two types of frequency inputs, AC sine
waves (magnetic coils type outputs) and Digital Square waves (Hall Effect
signals, contact closures), are acceptable.

All wiring connections are to be made inside of the junction box located on the
side of the C3V. liquid-tite connectors are supplied and should be used for the
external signal cables. The signal input wires are color coded to the type of
signal being used.