Fvs - flow verification system, 0 c3f external input / output signal connection, Page 8 page 9 – Xylem C3V CHEMICAL METERING PUMPS User Manual

Page 9: Sensor sold separately)

Advertising
background image

Page 8

Page 9

C3

C3

5.4

FVS - Flow Verification System

The C3 is equipped with a Flow Verification System which is designed to stop
the pump and provide a contact closure output in the event the sensor does not
detect flow during pump operation. This could indicate a clogged injection fitting,
empty chemical solution tank, loose tubing connection, etc.
To allow the pump to clear any gasses that may have accumulated during
stopper operation (such as with chlorine), an alarm delay time value from 1-255
seconds must be programmed (An alarm delay value of 000 seconds disables
the FVS system).

- (sensor sold separately)

Install the FVS Flow Sensor - The Flow Verification Sensor (FVS) should be
installed on the outlet (discharge) side of the pump head valve.
Connect the red/white, black, and white wires from the sensor to the red, black,
and yellow wires located in the pump’s junction box.

300-3000

FV-400-1V

500-5000

FV-500-1V

700-7000

FV-600-1V

Sensor

Model

Number

Operating Flow Range

mL/min

4.8-47.5

7.9-79.3

11.1-111

GPH (US)

Contact Closure Alarm Output - A contact closure output (relay) is provided
with the FVS system. The relay can be configured for normally open (factory
default) or normally closed operation by properly positioning the connector plug
on the circuit board .

Adapter

½” barb
½” barb
½” barb

Maximum
PSI / BAR

150 / 10.3
150 / 10.3
150 / 10.3

300-3000

300-3000

FV-400-2V

500-5000

500-5000

FV-500-2V

700-7000

700-7000

FV-600-2V

FV-400-3V
FV-500-3V

FV-600-3V

4.8-47.5

4.8-47.5

7.9-79.3

7.9-79.3

11.1-111

11.1-111

½” M/NPT
½” M/NPT

½” M/NPT

½” F/NPT

½” F/NPT

½” F/NPT

150 / 10.3
150 / 10.3

150 / 10.3

150 / 10.3

150 / 10.3

150 / 10.3

C3V | Diaphragm Metering Pump

Made in the USA

MODE

PRIME

Program

Minimum

Maximum

Blue-White Ind.

IP66

NEMA 4X

FVS

Sensor

SIGNAL INPUT/OUTPUT WIRE COLOR CODES

WIRE COLOR CODE

INPUT TYPE

FLOW VERIFICATION SENSOR (FVS)

ALARM RELAY

connect 2-conductor plug to either

normally open (NO) (factory default)

or normally closed (NC) side of receptacle.

3 AMP MAX @ 125VAC (24VDC)

PURPLE & PURPLE

RED/WHITE (+ 20VDC)

BLACK (-)

YELLOW (signal)

6.0 C3F External Input / Output Signal Connection

Advertising