Chem-pro, 5 operating mode 4 - frequency (hz) mode, Page 18 page 19 – Xylem C3V CHEMICAL METERING PUMPS User Manual

Page 18: Mode 3 programming examples, continued, Mode 4

Advertising
background image

Page 18

Page 19

C3

C3

4 Enter the motor speed at the minimum Hz input signal value.

Press the DOWN button to select the digit to program. The digit will blink
when selected.

Press the UP button to change the selected digit.

Repeat until all digits are programmed.

Program

Minimum

Maximum

Press the MODE button. The % SPEED icon will stop
blinking and the Hz icon will blink indicating the
minimum Hz value is ready to be programmed. The
currently programmed minimum value is shown on
the LCD.

4 Enter the minimum Hz input signal value (to the nearest 10 Hz).

Note: this value must be less than the maximum Hz input signal value.

Press the DOWN button to select the digit to program. The digit will blink
when selected.

Press the UP button to change the selected digit.

Repeat until all digits are programmed.

MODE

MODE

MODE

Press the MODE button. The Hz icon will stop
blinking and the % SPEED icon will blink. The
ARROW next to the word MAXIMUM will blink
indicating the maximum value is ready to be pro-
grammed. The Currently programmed maximum
motor speed value is shown on the LCD.

4 Enter the motor speed at the maximum VDC input signal value.

Press the DOWN button to select the digit to program. The digit will blink
when selected.

Press the UP button to change the selected digit.

Repeat until all digits are programmed.

Press the MODE button. The % SPEED icon will stop blinking and the Hz
icon will blink indicating the maximum Hz value is ready to be programmed.
The currently programmed maximum value is shown on the LCD.

4 Enter the maximum Hz input signal value (to the nearest 10 Hz).

Note: this value must be greater than the minimum Hz input signal value.

Press the DOWN button to select the digit to program. The digit will blink
when selected.

Press the UP button to change the selected digit.

Program

Minimum

Maximum

Mode 3 Programming Examples, continued

0%

25%

50%

75%

100%

P

u

m

p

O

u

tp

u

t

M

o

to

r

S

p

e

e

d

VDC input

from external source

0%

Output

Example 2

0 VDC will result in a pump output of
90%

10 VDC will result in a pump output of
0.0%

0

10

90%
Output

2

4

6

8

2

4

6

0%

25%

50%

75%

100%

P

u

m

p

O

u

tp

u

t

M

o

to

r

S

p

e

e

d

VDC input

from external source

100%

Output

Example 3

0 VDC will result in a pump output of
0.0%

10 VDC will result in a pump output of
100.0%

0

8

0%

Output

10

7.5

OPERATING MODE 4 - Frequency (Hz) Mode

Also known as Pulse Input. In this mode, the pump’s motor speed is adjusted
automatically based on the frequency (Hz) of the input signal. Any motor speed
can be assigned to either the minimum or maximum Hz input signals.

4 Set the pump for mode 4.

Press the MODE button until MODE 4
is shown on the LCD display.

The % SPEED or Hz icon will light
depending on the current display
setting.

The large LCD will indicate the current
motor speed or the Hz input value.

4 Enter the programming mode.

While MODE 4 is displayed, press and
hold the MODE button for more than
two seconds.

tm

CHEM-PRO

C3V | Diaphragm Metering Pump

Made in the USA

MODE

PRIME

Program

Minimum

Maximum

Blue-White Ind.

IP66

NEMA 4X

Mode 4

MODE

Blinking ARROW’s will point to the word PROGRAM and MINIMUM
indicating the program mode is activated and the minimum value is ready to
be programmed. The % SPEED icon will blink indicating the percentage of
speed is ready to be programmed.

MODE

Advertising
This manual is related to the following products: