TRANSFORMER SIZES
A full three phase supply is recommended for all three phase

motors, consisting of three individual transformers or one three

phase transformer. “Open” delta or wye connections using only

two transformers can be used, but are more likely to cause prob-

lems from current unbalance.
Transformer ratings should be no smaller than listed in the table

for supply power to the motor alone.

TRANSFORMER CAPACITY REQUIRED

FOR SUBMERSIBLE MOTORS

Smallest KVA Rating –

Submersible

Total Effective

Each Transformer

3Ø Motor

KVA

Open WYE

WYE or

HP Rating

Required

DELTA 2

DELTA 3

Transformers Transformers

1

1

2

3 2 1

2 4 2 1

1

2

3 5 3 2

5

7

1

2

5 3

7

1

2

10 7

1

2

5

10 15 10 5

15 20 15 7

1

2

20 25 15 10

25 30 20 10

30 40 25 15

40 50 30 20

50 60 35 20

60 75 40 25

75 90 50 30

100

120

65

40

AGENCY LISTINGS AND POWER CORD PLUG REMOVAL
Our single-phase sump, effluent and sewage pumps with 115,

208 and 230 volt motors up to and including 1 HP are now

built with NEMA three-prong grounding plug power cords. This

allows qualified electricians or professional pump installers to

easily connect the pumps; according to U.S. National (NEC),

Canadian (CSA), state, provincial and local electrical codes, to a

properly rated piggyback float switch for automatic operation.

NOTICE: This statement is written for the intent purpose of

verifying to electrical inspectors that according to both UL and

CSA standards it is allowable to remove the plug ends for direct

wiring to a disconnect switch, control panel or hard wired float

switch. Removing the plug end does not violate our UL Listing

or CSA/CUS certification in any way. Always follow the afore-

mentioned codes when making connections to the bare leads

once the plug is removed. Plug removal information and wiring

diagrams may be found in the Installation Manual supplied with

the pump and in this booklet. Please use this statement in the

event an inspector needs written assurance of this policy.

Electrical Data