Xylem Wastewater (Technical Manual) User Manual
Page 25
![background image](/manuals/311035/25/background.png)
PAGE 25
Wastewater
Goulds Water Technology, Bell & Gossett,
Red Jacket Water Products, CentriPro
L1
L2
N
GND
115/230 VAC (FOR 115 VAC, USE TERMINALS L1 AND N, JUMP L2 AND N).
SINGLE PHASE, 60 Hz
S1
J1
NOTE: WHEN USING SEPARATE 115 VAC CONTROL POWER SUPPLY, REMOVE
JUMPER (J1) FROM TERMINALS (L1) AND LL1). CONNECT 15 AMP MAX.
PROTECTED 115 VAC SUPPLY TO TERMINALS (LL1) AND (N) WITH
THE NEUTRAL OF THE SUPPLY TO (N).
LL1
CONTROL
ON-OFF
1
2
3
OFF FLOAT
ON FLOAT
ALARM FLOAT
4
TEST
S1-AUX
RUN
AUTO
OFF
HAND
S1
HIGH LEVEL
HORN *
ON - OFF
HORN
A 230 VOLT SYSTEM
REQUIRES A 4 WIRE
POWER SUPPLY LINE
L1, L2, N AND GND.
WITHOUT A NEUTRAL THE
CONTROL CIRCUIT
WILL NOT WORK.
T1
T2
PUMP
*NOTE: THE HORN ON/OFF SELECTOR SWITCH MUST BE PLACED
BACK INTO THE (ON) POSITION AFTER THE ALARM
CONDITION HAS BEEN CORRECTED IN ORDER TO
MAINTAIN THE AUDIO ALARM ANNUNCIATION
NOTE: The standard panels shown in this book are not designed to be used with pumps requiring external capacitors.
See the catalog for panels with built-in capacitor packs.
Simplex Single Phase Wiring Diagram – S10020
Before October 1, 2003