Application – three phase unbalance – Xylem Wastewater (Technical Manual) User Manual

Page 12

Advertising
background image

PAGE 12

Wastewater

Goulds Water Technology, Bell & Gossett,

Red Jacket Water Products, CentriPro

Hookup 1

Hookup 2

Hookup 3

L1 L2 L3

L1 L2 L3

L1 L2 L3

Starter

Terminals

T1 T2 T3

T1 T2 T3

T1 T2 T3

Motor

Leads

R B W

W R B

B W R

T3 T1 T2

T2 T3 T1

T1 T2 T3

Example:

T3-R = 51 amps

T2-W = 50 amps

T1-B = 50 amps

T1-B = 46 amps

T3-R = 48 amps

T2-W = 49 amps

T2-W = 53 amps

T1-B = 52 amps

T3-R = 51 amps

Total = 150 amps

Total = 150 amps

Total = 150 amps

÷ 3 = 50 amps

÷ 3 = 50 amps

÷ 3 = 50 amps

— 46 = 4 amps

— 48 = 2 amps

— 49 = 1 amps

4 ÷ 50 = .08 or 8%

2 ÷ 50 = .04 or 4%

1 ÷ 50 = .02 or 2%

THREE PHASE POWER UNBALANCE

A full three phase supply is recommended for all three phase

motors, consisting of three individual transformers or one three

phase transformer. So-called “open” delta or wye connections

using only two transformers can be used, but are more likely to

cause problems, such as poor performance overload tripping or

early motor failure due to current unbalance.
Transformer ratings should be no smaller than listed in Table 2

on page 3 for supply power to the motor alone.

Checking and correcting rotation and current unbalance
1. Establish correct motor rotation by running in both directions.

Change rotation by exchanging any two of the three motor

leads. The rotation that gives the most water flow is always

the correct rotation.

2. After correct rotation has been established, check the current

in each of the three motor leads and calculate the current

unbalance as explained in 3 below.
If the current unbalance is 2% or less, leave the leads as con-

nected.
If the current unbalance is more than 2%, current readings

should be checked on each leg using each of the three pos-

sible hook-ups. Roll the motor leads across the starter in the

same direction to prevent motor reversal.

3. To calculate percent of current unbalance:

A. Add the three line amp values together.
B. Divide the sum by three, yielding average current.
C. Pick the amp value which is furthest from the average cur-

rent (either high or low).

D. Determine the difference between this amp value (furthest

from average) and the average.

E. Divide the difference by the average.

Multiply the result by 100 to determine percent of

unbalance.

4. Current unbalance should not exceed 5% at service factor load

or 10% at rated input load. If the unbalance cannot be cor-

rected by rolling leads, the source of the unbalance must be

located and corrected. If, on the three possible hookups, the

leg farthest from the average stays on the same power lead,

most of the unbalance is coming from the power source. How-

ever, if the reading farthest from average moves with the same

motor lead, the primary source of unbalance is on the “motor

side” of the starter. In this instance, consider a damaged cable,

leaking splice, poor connection, or faulty motor winding.

Phase designation of leads for CCW rotation viewing

shaft end
To reverse rotation, interchange any two leads.
Phase 1 or “A” – Black Motor Lead or T1
Phase 2 or “B” – White Motor Lead or T2
Phase 3 or “C” – Red Motor Lead or T3
Notice: Phase 1, 2 and 3 may not be L1, L2 and L3.

FIGURE 12

OPEN DELTA

FULL THREE

PHASE

Application – Three Phase Unbalance

Advertising