Xylem Wastewater (Technical Manual) User Manual

Page 20

Advertising
background image

PAGE 20

Wastewater

Goulds Water Technology, Bell & Gossett,

Red Jacket Water Products, CentriPro

L1

L2

N

GND

25 A

25 A

S1

S2

1T

1

2

2T

1

2

PUMP NO. 2

PUMP NO. 1

WHITE

CONTROL

ON-OFF

BLACK

BLACK

YELLOW

ORANGE

HAND

OFF

AUTO

BLUE

S2

RUN

HAND

OFF

AUTO

PURPLE

S1

RUN

RED

TEST

RED

YEL
YELLOW

BRW
BROWN

TEST

MUTE

RESET

SILENCE

RESET

HORN

FLASH

PINK
WHITE

RED

FLASHING

SONALERT

OFF

LEAD

LAG

ALARM

R1

R2

C

L1

N

BLACK

H

L1

N

1

2

3

4

5

6

7

8

9

10

11

J1➀

OFF FLOAT➁

LEAD FLOAT

LAG FLOAT

(OPTIONAL)③

ALARM FLOAT

J2

DRY CONTACTS

FACTORY WIRED FOR (3) FLOAT

OPERATION. FOR (4) FLOAT

OPERATION, REMOVE JUMPER (J2)

FROM TERMNALS (6) AND (8). INSTALL

LAG FLOAT ON

TERMINALS (5) AND (6).

FOR SEPARATE 120 VAC

CONTROL POWER SUPPLY,

REMOVE JUMPER (J1) FROM

TERMINALS (H) AND (L1).

CONNECT 15 AMP MAX.

PROTECTED 120 VAC SUPPLY

TO TERMINALS (L1) AND (N).

WITH THE NEUTRAL OF THE

SUPPLY TO (N).

FOR USE WITH WIDE ANGLE

FLOAT SWITCH (ONE FLOAT FOR

BOTH ON AND OFF OPERATION).

JUMP TERMINALS (3) AND (4),

INSTALL WIDE ANGLE FLOAT TO

TERMINALS (1) AND (2).

FOR 120 VOLT OPERATION

USE TERMINALS (L1) AND (N)

JUMP TERMINALS (N) AND (L2)

230 VAC

SINGLE PHASE

60 Hz

A 230 VOLT SYSTEM
REQUIRES A 4 WIRE
POWER SUPPLY LINE
L1, L2, N AND GND.
WITHOUT A NEUTRAL
THE CONTROL CIRCUIT
WILL NOT WORK.

ALTERNATOR SWITCH

PUMP 1
ALT
PUMP 2

ALTERNATOR SWITCH –

STANDARD ON ALL DUPLEX

PANELS, THIS SWITCH PROVIDES

OPTIONS FOR: ALTERNATE

PUMPS, USE ONLY PUMP 1 OR

USE ONLY PUMP 2. IT IS USED

WHEN A PUMP IS REMOVED

FOR SERVICE.

NOTE: The standard panels shown in this book are not designed to be used with pumps requiring external capacitors.

See the catalog for panels with built-in capacitor packs.

Duplex Single Phase Wiring Diagram – D10020