Duplex three phase panel layout – d3 – Xylem Wastewater (Technical Manual) User Manual

Page 23

Advertising
background image

PAGE 23

Wastewater

Goulds Water Technology, Bell & Gossett,

Red Jacket Water Products, CentriPro

CB1

CB2

L1

L2

208/230/460/575 VAC

THREE PHASE

60 Hz

PUMP

NO. 1

PUMP

NO. 2

J1➀

FOR SEPARATE 120 VAC

CONTROL POWER SUPPLY,

REMOVE JUMPER (J1) FROM

TERMINALS (H) AND (L1).

CONNECT 15 AMP MAX.

PROTECTED 120 VAC SUPPLY

TO TERMINALS (L1) AND (N).

WITH THE NEUTRAL OF THE

SUPPLY TO (N).

H L1 N

1

2

3

4

5

6

7

8

9 10 11

J2

DRY CONTACTS

OFF FLOAT

LEAD FLOAT

LAG FLOAT

(OPTIONAL)③

ALARM FLOAT

FACTORY WIRED FOR (3) FLOAT

OPERATION. FOR (4) FLOAT

OPERATION, REMOVE JUMPER (J2)

FROM TERMINALS (6) AND (8).

INSTALL LAG FLOAT ON

TERMINALS (5) AND (6).

R1

R2

C

L1

ALARM

LAG

OFF

LEAD

TEST

MUTE

RESET

FLASHING

SONALERT

N

L3

1T1 1T2 1T3 2T1 2T2 2T3

S1

S1

OFF

CONTROL

PUMP 1

PUMP 2

ON

AUTO
OFF
HAND

TERMINAL BLOCK

208

230

460

575

TRANSFORMER

2 A

FACTORY WIRED FOR 460 VAC. FOR 208,230 OR

575 VAC OPERATION, CHANGE CONTROL TRANSFORMER

PRIMARY AT TERMINAL BLOCK.

ALTERNATOR SWITCH

PUMP 1
ALT
PUMP 2

ALTERNATOR SWITCH – STANDARD

ON ALL DUPLEX PANELS, THIS SWITCH

PROVIDES OPTIONS FOR: ALTERNATE

PUMPS, USE ONLY PUMP 1 OR USE

ONLY PUMP 2. IT IS USED WHEN A

PUMP IS REMOVED FOR SERVICE.

Duplex Three Phase Panel Layout – D3 — — — —