Xylem Wastewater (Technical Manual) User Manual

Page 21

Advertising
background image

PAGE 21

Wastewater

Goulds Water Technology, Bell & Gossett,

Red Jacket Water Products, CentriPro

OFF

CONTROL

PUMP 1

PUMP 2

ON

AUTO
OFF
HAND

CB1

CB2

S1

S2

1

2

1

2

1T

2T

L1

L2

N

120/230 VAC ➁

SINGLE PHASE

60 Hz

FOR 120 VAC OPERATION,

USE TERMINALS L1 AND N,

JUMP TERMINALS L2 AND N.

PUMP

NO. 1

PUMP

NO. 2

J1➀

FOR SEPARATE 120 VAC

CONTROL POWER SUPPLY,

REMOVE JUMPER (J1) FROM

TERMINALS (H) AND (L1).

CONNECT 15 AMP MAX.

PROTECTED 120 VAC SUPPLY

TO TERMINALS (L1) AND (N).

WITH THE NEUTRAL OF THE

SUPPLY TO (N).

R1

R2

C

L1

OFF

LEAD

LAG

ALARM

TEST

MUTE

RESET

FLASHING

SONALERT

N

H

L1 N

1

2

3

4

5

6

7

8

9 10 11

J2

DRY CONTACTS

OFF FLOAT

LEAD FLOAT

LAG FLOAT

(OPTIONAL)③

ALARM FLOAT

FACTORY WIRED FOR (3) FLOAT

OPERATION. FOR (4) FLOAT

OPERATION, REMOVE JUMPER (J2)

FROM TERMINALS (6) AND (8).

INSTALL LAG FLOAT ON

TERMINALS (5) AND (6).

ALTERNATOR SWITCH

PUMP 1
ALT
PUMP 2

ALTERNATOR SWITCH –

STANDARD ON ALL DUPLEX

PANELS, THIS SWITCH PROVIDES

OPTIONS FOR: ALTERNATE

PUMPS, USE ONLY PUMP 1 OR

USE ONLY PUMP 2. IT IS USED

WHEN A PUMP IS REMOVED

FOR SERVICE.

NOTE: Panel is not to be used with

pumps that do not include capacitors.

Duplex Single Phase Panel Layout – D10020