Friction loss – Xylem Wastewater (Technical Manual) User Manual

Page 5

Advertising
background image

PAGE 5

Wastewater

Goulds Water Technology, Bell & Gossett,

Red Jacket Water Products, CentriPro

Storage of Water in Various Size Pipes

Pipe Size

Volume in

Pipe Size

Volume in

Gallons per Foot

Gallons per Foot

1

1

4

.06 6 1.4

1

1

2

.09 8 2.6

2

.16

10

4.07

3

.36

12

5.87

4

.652

Minimum Flow to Maintain 2ft./sec. *Scouring Velocity in Various Pipes

Pipe Size

Minimum GPM

Pipe Size

Minimum GPM

1

1

4

9 6 180

1

1

2

13 8 325

2

21

10

500

3

46

12

700

4

80

* Failure to maintain or exceed this velocity will result in clogged pipes.

Based on schedule 40 nominal pipe.

PIPE VOLUME AND VELOCITY

Example:

(A) 100 ft. of 2" plastic pipe with one (1) 90º elbow and one (1) swing check

valve.

90º elbow – equivalent to

5.5 ft. of straight pipe

Swing check – equivalent to

13.0 ft. of straight pipe

100 ft. of pipe – equivalent to

100 ft. of straight pipe

118.5 ft. = Total equivalent pipe

Figure friction loss for 118.5 ft. of pipe.

(B) Assume flow to be 80 GPM through 2" plastic pipe.

1. Friction loss table shows 11.43 ft. loss per 100 ft. of pipe.

2. In step (A) above we have determined total ft. of pipe to be 118.5 ft.

3. Convert 118.5 ft. to percentage 118.5 ÷ 100 = 1.185

4. Multiply 11.43

x 1.185

13.54455 or 13.5 ft. = Total friction loss in this system.

EQUIVALENT NUMBER OF FEET STRAIGHT PIPE FOR DIFFERENT FITTINGS

Size of fittings, Inches

½"

¾" 1" 1¼" 1½" 2" 2½" 3" 4" 5" 6" 8" 10"

90°

Ell

1.5 2.0 2.7 3.5 4.3 5.5 6.5 8.0 10.0 14.0 15 20 25

45°

Ell

0.8 1.0 1.3 1.7 2.0 2.5 3.0 3.8 5.0 6.3 7.1 9.4 12

Long

Sweep

Ell

1.0 1.4 1.7 2.3 2.7 3.5 4.2 5.2 7.0 9.0 11.0 14.0

Close

Return

Bend

3.6 5.0 6.0 8.3 10.0 13.0 15.0 18.0 24.0 31.0 37.0 39.0

Tee-Straight

Run

1 2 2 3 3 4 5

Tee-Side Inlet or Outlet

3.3 4.5 5.7 7.6 9.0 12.0 14.0 17.0 22.0 27.0 31.0 40.0

or Pitless Adapter
Ball or Globe Valve Open

17.0

22.0

27.0

36.0

43.0

55.0

67.0

82.0

110.0

140.0

160.0

220.0

Angle

Valve

Open

8.4 12.0 15.0 18.0 22.0 28.0 33.0 42.0 58.0 70.0 83.0 110.0

Gate

Valve-Fully

Open

0.4 0.5 0.6 0.8 1.0 1.2 1.4 1.7 2.3 2.9 3.5 4.5

Check

Valve

(Swing)

4 5 7 9 11 13 16 20 26 33 39 52 65

In Line Check Valve
(Spring)

4 6 8 12 14 19 23 32 43 58

or Foot Valve

Friction Loss

Advertising