IPCP 505 • SIS Programming and Control
56
X6#
= Pulse time in 20 ms increments. If this parameter is
missing or = 0, then pulse length = default =
25 = 500 ms. 1 = 20 ms (minimum pulse time)
to 65535 = 1310700 ms (maximum pulse time).
X6(
= IP connection timeout period specified in
10-second steps (1 - 65000, default = 30 =
300 seconds). If no data is received during
the specified period, the Ethernet connection
closes. Responses are returned with leading
zeros.
X7)
= The number (0 - 65535) to insert into an
e-mail message if an *.eml file has
an embedded server-side include
“<!--#echo var = “WCR
|
” -->” (the
E
CR
}
command with no parameters)
The numeral is a 16-bit number to be employed
as the user defines.
This is an optional parameter. Use 0 as a
placeholder if the optional
X4&
variable is used
but
X7)
is not needed.
Maximum = 65535.
X7#
= An e-mail account username of up to 31
characters. Do not use commas. This parameter
is optional during setup and is used for SMTP
authentication.
X7$
= An e-mail account password (for SMTP
authentication) of up to 31 characters.
Do not use commas. This parameter is optional
during setup. If a password is set, the response
is not the actual password characters but
asterisks (****).
X8%
= Switched output power load status:
0 = ok (total power draw <40 watts)
1 = at limit (total power draw is 40-44 watts)
2 = fault/overload (total power draw >44 watts)
X8^
= Switched output power use:
total power drawn from all power output ports =
nnn, in tenths of watts
X8&
= Switched output power group:
0 = no group
1 = group 1
2 = group 2
X21)
= IR/serial port configuration type
0 = IR port (default, 0 – 5 VDC)
1 = RS-232 port (±5 VDC)
NOTE: For commands and examples of computer or device responses mentioned in this guide, the
character “0“ is used for the number zero and “O“ represents the capital letter “o”.