Franklin Fueling Systems T5 Series Fuel Management System Programming Guide User Manual
Page 30

26
Relay Modules
The Relay Module is a non-intrinsically safe module that has 8 identical Form C output channels. Each channel has a fuse
and three terminals. Each channel can be configured as NO or NC with the power off by wiring to the appropriate terminals.
Group Name
Parameter Name
Parameter
Default
Description
Parameter
Input
Relay Modules
Module #
10 Amp
Channels
(No)
(0)
Select Yes if this is the 10 Amp relay module.
Number of relays used on this module.
Yes / No
0-8 (2 Amp
module)
0-6 (10 Amp
Module)
Channel #
Name
(Relay 1)
Given name of the channel.
abc#
Enabled
(Yes)
Yes if the channel is in use.
Yes / No
Type
(Unknown)
Equipment connected to the relays output.
Unknown
Submersible
Alarm
Solenoid
Dispenser
Other
Polarity
(Normal)
Allows the polarity to be inverted.
Normal, Invert
Logic
(OR Logic)
The type of logic that the gate will use to process incoming signals.
OR, AND, XOR
Physically Wired As (Normally Open)
How the relay is wired externally.
NO, NC
Number of inputs
(0)
Number of devices that can control the relay.
1-32
Input #
Type
(Unknown)
Type of module that is sending the signal.
Unknown
Controller
Power Supply
AC Input
IO
Probe
2-wire Sensor
3-wire Sensor
4-20 mA