4 terminal block wiring – Alpha Technologies Continuity: 6K_10K User Manual
Page 17

15
0170012-J0 Rev A
3.4 Terminal Block Wiring
Continuity 6K model
Continuity 10K model
TB1
TB2
L11-N1:
Terminals for bypass input that provides power to the
loads when the UPS is working in the bypass mode.
L12-N1
Terminals for the utility input that provides power to the
loads when the UPS is in the Utility mode.
G1:
Terminal for the UPS input ground.
L21 ~ N22:
Terminals for the UPS output.
G2:
Terminal for the UPS output ground.
Remarks:
• The maximum output current for each terminal is 30 Amps for the 6 kVA model and 50 Amps for the
10 kVA model.
• If the UPS is a DIM (dual input mode) type whose utility and bypass sources are the same, L11 and
L12 must to be shorted for 1-phase input models.
• If the UPS is a SIM (single input mode) type, only the AC source can be hooked up to the UPS via
the L12-N1 terminal for a 1-phase input model.
• Use cable ties to secure the cables.
Figure 2 — 1-phase terminal block wiring