B.2.2. Selecting an Installation Position
Air flow within the unit is from the front to back. Select an installation position that has good ventilation with at least
30 cm clearance around the equipment.
Figure 1 Installation position
B.2.3. Wiring
Refer to the following table for cable and breaker sizes:
Model
Maximum
Current
Circuit
Breaker
Wire Size
AC input and Output
6KVA
33A
40A
AWG #8
10KVA
54.3
63A
AWG #6
Battery input
6KVA
25A
30A
AWG #10
10KVA
41
63A
AWG #10