Alpha Technologies Continuity: 6K_10K User Manual
Page 21

19
0170012-J0 Rev A
3.5.2 Start-up in Battery Mode (Cold Start)
1. Make sure the UPS has at least 1 set (20 pcs) of 12 V / 7 Ah batteries installed.
2. Press and hold the UPS On
button for approximately 5 seconds. The buzzer sounds twice. The LCD
display scrolls from Screen A to Screen G.
3. Press and hold the UPS On
button again for about 3 seconds until the LCD display scrolls from
Screen G to Screen H. The UPS is in the self-test mode and can supply power to the output after about a
minute. The LCD display will scroll to Screen I.
If a failure occurs within 15 seconds of pushing the UPS On button, the UPS will automatically switch off.
Screen G
Off means the UPS pre-start has
been successful.
Screen H1
Utility input is 0 and abnormal.
Screen H2