0170012-J0 Rev A
18
8. Press and hold the UPS On
button for approximately 3 seconds. The buzzer sounds twice and the
LCD display scrolls from Screen B to Screen C.
Screen C
9. The UPS is in self-test mode again. The LCD display scrolls from Screen C to Screen D and remains in
the battery mode for approximately 4 seconds. The display scrolls from Screen E1 to Screen F if the self-
test is successful.
Screen D
Screen E1
Screen E2
Screen F
Test
OK in self test
If the self-test fails, the LCD
display scrolls from Screen D to
Screen E2. An error code or sta-
tus is shown on the screen
220 VAC in utility input
10. The UPS start-up operation is now complete. Charge the batteries for at least 8 hours to ensure they are
fully charged.