0170012-J0 Rev A

18

8. Press and hold the UPS On

button for approximately 3 seconds. The buzzer sounds twice and the

LCD display scrolls from Screen B to Screen C.

Screen C

9. The UPS is in self-test mode again. The LCD display scrolls from Screen C to Screen D and remains in

the battery mode for approximately 4 seconds. The display scrolls from Screen E1 to Screen F if the self-

test is successful.

Screen D

Screen E1

Screen E2

Screen F

Test

OK in self test

If the self-test fails, the LCD

display scrolls from Screen D to

Screen E2. An error code or sta-

tus is shown on the screen

220 VAC in utility input

10. The UPS start-up operation is now complete. Charge the batteries for at least 8 hours to ensure they are

fully charged.