0170012-J0 Rev A

Page 43

B.3. Installation

Take the following steps to minimize EMI when wiring:
1. Make sure the input and output cables and the battery cables are kept separate from each other to avoid

unnecessary noise interference.

2. Keep the path of the communication cables (RJ45, RS232, RS485, USB, EPO and Shutdown) separate from

the I/O and battery cables. If unavoidable, place them at 90 degrees to each other and at least 20cm apart.

Figure 2 Cabling

3. The UPS is equipped with an EMI filter. To prevent potential current leakage hazard, ensure that the AC main

supply is securely grounded.

B.4. Start-up Procedure

1. Position the units as shown in Figure 1.
2. Use communication cables that are less than 7M long, connected as a “Ring” loop.

Figure 3

INPUT

OUTPUT

CONTROL

CONTROL

CONTROL

CONTROL

I

O

I

O

I

O

I

O

1050mm RJ-45 communication connecting wire
1900mm RJ-45 communication connecting wire

Max. 25M; all Input Power cables should be the same length.

Max. 25M, all Output Power cables should be the same

Incorrect

Correct

A

B

90°

20cm

B

A

B

A

A  Communication or Control signal wires

B  Power wires & cables