A.5.3. Output Wiring Description

The maximum output current for each terminal is 30A (6K) or 50A (10K).
When the wiring of the TR OUTPUT block corresponds to drawing (a) and the input of L2-N2 from the UPS

OUTPUT block is 200Vac, 220Vac, 230Vac or 240Vac, the output voltage is 100Vac, 110Vac, 115Vac or 240Vac.

If the input of L2-N2 from UPS OUTPUT block is 208Vac, the output is 120Vac.
When the wiring of the TR OUTPUT block corresponds to drawing (b) and the input of L2-N2 from the UPS

OUTPUT block is 200Vac, 220Vac, 230Vac or 240Vac, the output voltage is 200/100Vac, 220/110Vac, 230/115Vac

or 240/120Vac. If the input of L2-N2 from UPS OUTPUT block is 208Vac, the output voltage is

240Vac/208Vac/120Vac.

N22

L22

N11

L12

240Vac

(b)

120Vac

120Vac

208Vac

L11

N22

L22

N11

110Vac

(a)

L12

L11

6KVA (Max)

6KVA (Max)

6KVA (Max)

3KVA (Max)