Alpha Technologies Continuity: 6K_10K User Manual
Page 42

0170012-J0 Rev A
Page 40
A.5.3. Output Wiring Description
The maximum output current for each terminal is 30A (6K) or 50A (10K).
When the wiring of the TR OUTPUT block corresponds to drawing (a) and the input of L2-N2 from the UPS
OUTPUT block is 200Vac, 220Vac, 230Vac or 240Vac, the output voltage is 100Vac, 110Vac, 115Vac or 240Vac.
If the input of L2-N2 from UPS OUTPUT block is 208Vac, the output is 120Vac.
When the wiring of the TR OUTPUT block corresponds to drawing (b) and the input of L2-N2 from the UPS
OUTPUT block is 200Vac, 220Vac, 230Vac or 240Vac, the output voltage is 200/100Vac, 220/110Vac, 230/115Vac
or 240/120Vac. If the input of L2-N2 from UPS OUTPUT block is 208Vac, the output voltage is
240Vac/208Vac/120Vac.
N22
L22
N11
L12
240Vac
(b)
120Vac
120Vac
208Vac
L11
N22
L22
N11
110Vac
(a)
L12
L11
6KVA (Max)
6KVA (Max)
6KVA (Max)
3KVA (Max)