0170012-J0 Rev A

4

• There is a risk of explosion if a battery is replaced by an incorrect type.
• Do not dispose of batteries in a fire—the batteries may explode. Dispose of used batteries accord-

ing to the battery manufacturer's instructions.

• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be

toxic.

• This UPS supports electronic equipment in offices, telecommunications, process control, medical

and security applications. Only authorized personnel must install the UPS in the following locations:

a. Medical applications directly related to human life

b. Elevators, metro (subway) system or any other equipment related to human safety

c. Public security system or critical computer systems

• Always switch off the UPS and disconnect the batteries before relocating the UPS. It may cause

electrical shocks if the output is not completely switched off.

• Do not open the UPS—there are no serviceable parts inside. Opening the UPS will void the warranty.
• Do not repair the UPS yourself Contact your local supplier. Opening the UPS will void the warranty.
• The UPS can be equipped with an optional Maintenance Bypass Switch. Follow the procedures

strictly to switch on/off the Maintenance Bypass Switch.

• The UPS offers CVCF (Constant Voltage Constant Frequency) setting function.

a. For correct setting and wiring, contact the Alpha technical service team (see chapter 8).

b. Do not do it yourself; otherwise, your warranty will be void.

• This UPS has been designed and constructed to protect your assets from the wide range of power

aberrations experienced on Utility power lines today. It is your insurance for reliable, clean and

stable voltage supply. It is worth taking care to install the system correctly and to have it maintained

correctly by your regional Alpha service center (see chapter 8).

To reduce the risk of fire, connect the unit input only to a circuit provided with branch

circuit over-current protection of 40A for 6KVA and 65A for 10KVA amperes rating in ac-

cordance with the National Electric Code, ANSI/NFPA 70.

CAUTION!

1.2  Storage Instruction

Store the UPS in a location where the temperature ranges between -15

ºC (+5ºF) to 40ºC (104ºF).

For extended storage in moderate climates, charge the external battery pack for 12 hours every 3

months. Repeat every 2 months if the ambient storage temperature is above 30

ºC (86ºF).

Disconnection Device - The customer must provide a disconnect switch for the AC

output circuit. To reduce the risk of fire, connect only to a circuit provided with branch

circuit over-current protection of 30 amperes for 6KVA and 40 amperes for 10KVA rating

in accordance with the National Electric Code, ANSI/NFPA 70. (See details in the follow-

ing table.)

CAUTION!