3 led indicators, 1 power on, 2 overload and overload fault – Alpha Technologies INVERTER 2000 User Manual

Page 12: 3 priority

Advertising
background image

Alpha Technologies Ltd.

014-129-B2 Rev C WC

© 2010 Alpha

Technologies Ltd. ALPHA is a registered trademark of Alpha Technologies Ltd. All Rights Reserved.

Page 6 of 19

Figure 4–USB connectivity

4.1.3 LED Indicators

Inverter Module LED Display Status
Priority

Green LED

LED Signal

Status

Solid

Inverter work normally

Blink (intermittent (slow))

One of the status as follows:

1) Power On.

Details refer to note.

2) Shut down remotely.

Priority

Yellow LED

LED Signal

Status

Blink (intermittent (slow))

Power On

Details refer to note.

Solid

One of the alarms as follows:

1) Over Load (Load > 105%);

2) DC input abnormal.

(Vin<=45V or Vin>=58V)

Blink (intermittent (fast))

Inverter shut down due to DC super

low/super high input.

(Vin<=VLVSD or Vin>=VHVSD)

Priority

Red LED

LED Signal

Status

Blink (slow)

One of the alarms as follows:

1) EEPROM Fault;

2) Inverter Fan Fault.

Blink (fast)

One of the alarms as follows:

1) Internal fault;

2) Temperature High.

Solid

One of the alarms as follows:

1) Input reverse polarity;

2) Inverter output Short circuit;

3) Abnormal output voltage;

4) Negative Power Protection;

5) Overload fault.

Table A–Inverter LED indicator display

4.1.3.1 Power On:

When the inverter is in “Power On” mode, the green LED and the yellow LED are flickering

synchronously without any alarm.

4.1.3.2 Overload and Overload Fault:

When overload fault alarm occurs, the yellow LED and red LED turn on at the same time, while

overload alarm occurs, only the yellow LED turns on.

4.1.3.3 Priority:

If more than one warning exists at the same time, then the LED will display the highest priority.