2 rear panel, 1 dc input, 2 ac input – Alpha Technologies INVERTER 2000 User Manual

Page 14: 3 ac input breaker, 4 ac output, Rear panel

Advertising
background image

Alpha Technologies Ltd.

014-129-B2 Rev C WC

© 2010 Alpha

Technologies Ltd. ALPHA is a registered trademark of Alpha Technologies Ltd. All Rights Reserved.

Page 8 of 19

4.2 Rear Panel

Located on the rear panel are the terminations for wiring:


Figure 5–Rear panel

4.2.1 DC Input

ST722B2502 (300 Volts (UL 1059 Class B and C) / 175 Amps)
Wire Range #2 - #8
(Accommodates two-hole compression lugs on 0.625" centers – wires #2 and larger may require narrow lugs)

Figure 6–DC input terminals

Connect to a 48Vdc battery or DC power source.

Upper terminal

【+】is positive, and【-】is negative. Reverse polarity connection will cause red alarm LED to

illuminate (indicator solid), but inverter will not be damaged.

4.2.2 AC Input

230Vac model: RECEPTACLE /WS-044-7 16A 250V INLET GAP1.5
120Vac model: cable P.C.#12*3C 20A 125Vac 5-20P UL 2200

4.2.3 AC Input Breaker

230Vac model: N.F.B1P15A 250Vac JOEMEX/PE747415-214D-051
120Vac model: NFB 1P20A/120Vac (CIRCUIT PROTECTOR) UL489

4.2.4 AC Output

230Vac model: AC output outlet IEC320-C13 10A 250Vac
120Vac model: REC. RON/RF-6005-A 5-20R 20A 125V 3P

Alarm output port

DC input terminal

Remote ON/OFF switch

AC output terminal

AC input terminal

AC input breaker

DC +

DC -

Parallel signal port

reserved and not

available