6

Default Values

Alarm Name

Level

Remark

Output Status

Inverter fault

Critical

Inverter fault

Off

Over load

Observe

Inverter over-loading

On

Over load fail

Critical

Over load shut down

Off

Inv fan fault

Major

Inverter fan fault

On

Power limit

Observe

Inverter power limited

On

DC abnormal

Observe

Inverter input out of range

On

DC low Inv off

Observe

Inverter shut down due to low input voltage

Off

Inv Bus High

Critical

Inverter Bus voltage over the maximum level

Off

Inv Bus Low

Critical

Inverter Bus voltage under the minimum level

Off

BusSoft fail

Critical

Inverter Bus soft start fail

Off

Output short

Critical

Inverter output short circuit

Off

Inv OPV Low

Critical

Inverter output voltage low

Off

Inv OPV High

Critical

Inverter output voltage high

Off

Inv Temp High

Critical

Inverter temperature high

Off

NegPow Protect

Critical

Inverter negative power protection

Off

SoftStart fail

Critical

Inverter soft start fail

Off

Mains abnormal

Observe

Mains unavailable

On

Eeprom fail

Major

Inverter EEPROM fault

On

Table H–Alarm default levels

NOTE: Critical level fault needs manual restart.

Setting

Default Value

ATS priority

On-line

230Vac Unit

Mains high loss volt

276V

Mains low loss volt

176V

Inverter output high loss volt

264V

Inverter output low loss volt

192V

Inverter shutdown due to low input volt

40V

Inverter shutdown due to high input volt

60V

Inverter output volt

230V

Inverter output volt frequency

50Hz

Inverter output power limit

100%

120Vac Unit

Mains high loss volt

138V

Mains low loss volt

89V

Inverter output high loss volt

140V

Inverter output low loss volt

90V

Inverter shutdown due to low input volt

40V

Inverter shutdown due to high input volt

60V

Inverter output volt

120V

Inverter output volt frequency

60Hz

Inverter output power limit

100%

System Parameter

LCD brightness value

45

Language

English

Password

0000

Table I–Inverter/System factory defaults