7 specifications, 1 dc input, 2 ac input (with transfer switch) – Alpha Technologies INVERTER 2000 User Manual

Page 22: 3 ac output, Pecifications, Dc input, Ac input (with transfer switch), Ac output, 7specifications

Advertising
background image

Alpha Technologies Ltd.

014-129-B2 Rev C WC

© 2010 Alpha

Technologies Ltd. ALPHA is a registered trademark of Alpha Technologies Ltd. All Rights Reserved.

Page 16 of 19

7

Specifications

7.1 DC Input

Nominal Voltage:

48Vdc

Operating Range:

40 to 60Vdc within rated limits

Under Voltage Warning Threshold: 45Vdc
Under Voltage Threshold:

40Vdc

Over Voltage Warning Threshold:

58Vdc

Over Voltage Threshold:

60Vdc

Inrush current:

<2 x I rated

Isolation DC-enclosure:

707Vdc (varistors and filter capacitor removed)/1min

Input Protection:

Reverse polarity protection

Psophometric Noise Voltage:

1.0mV ITU-T O.41 (16.66 to 6000Hz)

Wide Band Noise:

<1.0mV (psophometric, 25Hz to 5kHz)

<20mVrms (25Hz to 20kHz)

Peak to Peak Noise:

<150mV up to 100MHz

7.2 AC Input (with transfer switch)

Voltage Range:

110/115/120Vac: 89 to 138Vac

208/220/230/240Vac: 176 to 276Vac

Over Voltage Threshold:

276 / 138Vac

Under Voltage Threshold:

176 / 89Vac

Frequency Range:

50/60 ±2.5% Hz

Back-feed Protection:

Comply with safety requirement

Transfer Time:

8ms when Inverter → Mains AC

10ms when Mains AC → Inverter

7.3 AC Output

Power Capacity:

2000VA/2000W

Waveform:

Pure sine wave

Power Factor:

1.0

Nominal Output Voltage:

110/115/120Vac or 208/220/230/240Vac

Voltage Regulation:

±2%

Output Frequency:

50/60Hz

Frequency Variation:

±0.5%

Frequency Setting:

Manually, field-selectable

Crest Factor:

3:1

T.H.D. (Current):

<3% for linear load, <5% for non-linear load

Capacitive/Inductive Load:

-1.0 to +1.0 without exceeding permissible distortion for resistive load

Efficiency:

>91%

Current Limitation:

Electronic current limitation at overloads and short circuits

Isolation AC-enclosure:

Basic isolation (Pri-Gnd) 2121Vdc/1min

Isolation AC-DC:

Reinforced isolation (Pri-Sec) 4242Vdc/1min

Surge Protection:

EN61000-4-5, Telcordia GR-1089 CORE, ANSI/IEEE C62.41, STD 587-

1980

Dynamic Response:

Better than ±10% according to IEC 62040-3 Class 1

Advertising