Maintenance and Troubleshooting

5.1 Preventative Maintenance

The following preventive maintenance routines should be considered as a minimum requirement. Your installation

may require additional preventive maintenance to assure optimal performance from your installed inverter and

associated equipment. These routines should be performed twice a year (more often if required). We strongly

recommend a contract with Customer Support Services for preventive and remedial maintenance. The technician

or electrician performing preventive maintenance on the equipment must read and understand thoroughly this

manual and be familiar with the indicators, controls, and operation of the equipment.

5.2 Troubleshooting Guide

If the inverter fails to operate properly after having the installation and setup of the inverter thoroughly re-

examined, use the troubleshooting table to determine the probable cause(s) and solution(s) to resolve error

conditions. For unlisted error conditions, please contact your local dealer for technical assistance.

Error Condition

Possible Cause

Recommendation

No AC output

and all LEDs off.

Lack of input power.

Ensure input cables are all firmly connected to

power source.

Check if power source is not yet switched on, or

is low in power.

No AC output.

Both green and yellow

LEDs flicker.

Inverter self-diagnosis.

Inverter self-diagnosis takes a few seconds.

LED turns to a solid green light after the

completion of self-diagnosis.

No AC output.

Both yellow and red

LEDs are on.

Load exceeds 125%.

Ensure the load is no higher than 105% of the

total power rating. Reduce as required.

No AC output.

Red LED is on.

1. Input wiring is connected in reverse (i.e.

reverse polarity).

Ensure input cables are connected to correct

polarity (positive to positive, negative to

negative).

2. Internal fault.

Restart the unit. If it fails to work, return it to

factory for repair.

3. Inverter output is shorted.

Turn off the input power source to remove all

short circuits.

4. Negative Power Protection.

When transfer between Mains and inverter, mains

backfeed to inverter.

Red LED blinks fast.

1. Inverter fails to soft start.

Reboot the inverter system by switching off and

on the input power source.

2. Inverter temperature rises beyond the

temperature limit.

Leave inverter idle to cool down for few minutes.

AC output exists with

yellow LED flickering.

Input voltage is out of operating range.

Ensure input voltage is between 45 to 58Vdc.

AC output exists and

yellow LED is on.

Load is over 100% but below 125%.

Ensure the load is no higher than 105% of the

total power rating. Reduce as required.

Inverter continuously

delivers power, but with

red LED flickering

slowly.

Failure of EEPROM.

Reboot the inverter system by switching off and

on the input power source.

Fans failure.

Check if the fans are locked or fail to work.

If fan is locked, remove the obstruction;

if fan fails to work, replace the fan.

Table G–Troubleshooting for inverter module